Line Modules
4.3 Active Line Modules
4.3.3.3
Line/load connection
Table 4- 13
Line/load connection of the Active Line Module
Terminals
U1, V1, W1
3 AC power input
DCP, DCN
DC power output
PE connection
116
Technical specifications
Voltage:
3 AC 380 V -10 % (-15 % < 1 min) to 3 AC 480 V +10 %
•
3 AC 500 V -10 % (-15 % < 1 min) to 3 AC 690 V +10 %
•
Frequency: 47 Hz to 63 Hz
Connecting lugs:
Frame sizes FXL, GXL, HXL: d = 13 mm (M10/50 Nm) for cable lugs in accordance with
•
DIN 46234 / DIN 46235
Frame size JXL: d = 13 mm (M10/50 Nm) for busbar connection
•
Voltage:
570 to 720 VDC
•
750 to 1035 VDC
•
Connecting lugs: D = 13 mm (M10/50 Nm) for busbar connection
Connecting lugs:
Frame sizes FXL, GXL, HXL: D = 13 mm (M10/50 Nm) for cable lugs in accordance with
•
DIN 46234 / DIN 46235
Frame size JXL: D = 13 mm (M10/50 Nm) for busbar connection
•
Chassis Liquid Cooled Power Units
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1