Table 4- 21
Technical data for Active Line Modules, 380 V – 480 V 3 AC
Order number
Rated output
- for I
(50 Hz 400 V)
L DC
- for I
(50 Hz 400 V)
H DC
- for I
(60 Hz 460 V)
L DC
- for I
(60 Hz 460 V)
H DC
DC link current
- Rated current I
N DC
- Base load current I
L DC
- Rated current I
H DC
- Maximum current I
max DC
Input current
- Rated current at 400 V 3 AC
- maximum
Supply voltages
- Line voltage
- Line frequency
- Electronics power supply
- DC link voltage
Pulse frequency
Electronic power consumption (24 V DC)
Cooling method
Power loss, max.
2)
- at 50 Hz 400 V
- at 60 Hz 460 V
Max. coolant temperature
- Without derating
- With derating
Rated volumetric flow
for water at 70 kPa pressure drop
Liquid volume of integrated heat exchanger
DC link capacitance
- Active Line Module
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line/load connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC link connection (DCP, DCN)
- PE connection
Max. cable length
(total of all motor cables and DC link)
- shielded
- unshielded
Chassis Liquid Cooled Power Units
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
6SL3335–
kW
kW
hp
hp
A
A
A
A
1)
A
A
V
ACrms
Hz
V
DC
V
DC
kHz
A
kW
kW
°C
°C
l/min
3)
dm³
µF
dB(A)
mm²
mm²
mm²
m
m
7TE35–0AA3
7TE38–4AA3
300
500
450
750
500
700
400
700
549
941
535
917
489
837
823
1410
490
840
735
1260
380 V 3 AC -10 % (-15 % < 1 min) to 480 V 3 AC +10 %
24 (20.4 - 28.8)
4
2.5
1.5
1.6
Liquid cooling with integrated heat exchanger made of
Stainless
Aluminum
steel
3.1
5.3
3.36
5.75
45
45
50
50
12
16
0,91
0.74
9600
17400
52
54
Flat connector for M12 screw
2 x 240
4 x 185
Busbar
Busbar
2 x 240
4 x 185
2700
3900
4050
5850
Line Modules
4.3 Active Line Modules
47 to 63 Hz
1.5 x U
line
127