Commissioning
2.3 Basic Operator Panel 20 (BOP20)
BOP20 functions
Table 2- 4
Functions
Name
Backlighting
Changeover active drive
Units
Access level
Parameter filter
Selecting the operating
display
User parameter list
Unplug while voltage is
present
Actuating keys
68
The backlighting can be set using p0007 in such a way that it switches itself off automatically
after the set time if no actions are carried out.
From the BOP perspective the active drive is defined using p0008 or using the keys "FN" and
"Arrow up".
The units are not displayed on the BOP.
The access level for the BOP is defined using p0003.
The higher the access level, the more parameters can be selected using the BOP.
Using the parameter filter in p0004, the available parameters can be filtered corresponding to
their particular function.
Actual values and setpoints are displayed on the operating display.
The operating display can be set using p0006.
Using the user parameter list in p0013, parameters can be selected for access.
The BOP can be withdrawn and inserted under voltage.
The ON and OFF keys have a function.
When withdrawing, the drives are stopped.
Once the BOP has been inserted, the drives must be switched on again.
.
ON and OFF keys have no function
Withdrawing and inserting has no effect on the drives.
The following applies to the "P" and "FN" keys:
When used in a combination with another key, "P" or "FN" must be pressed first and then
the other key.
Description
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1