Commissioning
2.7 First commissioning, vector control mode in the chassis format
What to do?
6.
Motor temperature
7.
Save the parameters
on the device
8.
The motor starts to
run.
Diagnostics parameters (see the SINAMICS S120/S150 List Manual)
● r0002 Infeed/drive operating display
● r0046 Missing enable signals (for more information, see "Diagnostics")
104
How to do it?
Thermistor selection: via Motor Module (11)
Temperature sensor type: KTY84 (2)
Response to overtemperature: alarm and fault
(no reduction of I
)
max
Fault message for thermistor failure: ON
Deceleration time: 0.100 s
Alarm threshold: 120.0° C
Fault threshold: 155.0° C
Target device -> Copy from RAM to ROM
The drives can be started via the control panel in
STARTER.
Line/DC link identification will be carried out once
the pulses for the infeed have been enabled and
line/DC link identification has been activated. The
infeed then switches to operational mode.
When the pulses are enabled, a one-off motor
data identification run (if activated) is carried out.
When the pulses are enabled again, optimization
with a rotating motor (if activated) is carried out.
Position cursor on drive unit and
right-click.
For more information about the
control panel, see Getting Started.
During motor data identification, a
current flows through the motor,
which means that it can align itself
by up to a quarter of a revolution.
For more information about line/DC
link/motor data identification, see
the SINAMICS S120 Function
Manual.
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1