Communication via AS-i - only for G110M

7.1 Setting the address

Connection
The following table shows the AS-i plug assignment. Further connection information is
contained in the AS-Interface system manual.
Table 7- 1
7.1
Setting the address
As factory setting, all AS-i slaves have address 0. Slaves with address 0 are not included in
the communication.
The addresses must be unique, although they can be mixed as required.
You have the following options when making the address assignment:
● Automatic addressing via the AS-i master
● Addressing via the addressing device
● Addressing via parameters
Before you set the address, you must specify whether the inverter is integrated as Single
Slave or Dual Slave in the AS-i network.
● p2013 = 0: Single Slave (factory setting)
● p2013 = 2: Dual Slave
If for the commissioning you select the default setting 30 or 32 (Single Slave), or 31 or 34
(Dual Slave), p2013 is assigned the appropriate value.
Note
Changes made to p2012 and p2013
Changes made to the p2012 and p2013 parameters take effect immediately after the
change.
If you work with STARTER, you must save the changes via
not lost when the system is switched off.
202
Overview of the manuals (Page 235)
Pin assignment
X03 AS-i,
Pin
(M12, IP57)
1
2
3
4
5
Function
Description
AS-i +
AS-i plus signal
0 V
Reference potential for terminal 4
AS-i -
AS-i minus signal
24 V
24 V auxiliary voltage
Not assigned
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC