Siemens SINAMICS G110M Function Manual page 197

Fieldbuses
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Heartbeat
Principle of operation
The slave periodically sends heartbeat messages. Other slaves and the master can monitor
this signal. In the master, set the responses for the case that the heartbeat does not come.
Setting value for heartbeat
Set in p8606 the cycle time for the heartbeat in milliseconds.
Inverter behavior with a bus fault
With a bus fault, the CAN master goes to the "Bus OFF" status. In the inverter, set the
response to the bus error using parameter p8641. Factory setting: p8641 = 3 (AUS3).
If you have resolved the bus error, then you have the following options to restart
communication:
● You switch off the inverter power supply, wait until all of the LEDs on the inverter go dark,
and then you switch on the inverter power supply again.
This means that you withdraw the bus state and restart communication.
● You acknowledge the bus error via DI 2 or directly via p3981 and start the communication
either
– Manually by setting p8608[0] = 1. After starting, p8608 is internally set back to 0.
– Automatically every two seconds. To do this, you must have set p8608[1] to 1 when
Danger, as the motor cannot be stopped via the control when a bus error occurs
If you are working with parameter setting p8641 = 0 (no response for bus error), then for a
bus error, you cannot stop the motor via the control system.
For this case, wire an additional OFF command via terminals.
Fieldbuses
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
commissioning.
WARNING
Communication over CANopen
6.7 Integrating the inverter into CANopen
197