AO810, AO890
Default value is YES.
CLUSTER
Enter the I/O device cluster of the station where this module is located. The cluster
connected directly to the FCI is number zero (0). The number in this field is 0 -7.
Default value is 0.
DQ CYCLE TIME
Enter the channel data quality update period (msec) over the fieldbus. Refer to the
S800 I/O User's Guide for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048, and 4096
The default value is 128.
LABEL
Enter a characteristic name to identify the AO810 or AO890 Module of the station.
The name may contain up to 20 characters.
For the AO890 module, enter a description that includes the module type for
future reference to help alleviate confusion with an AO890 being used in the
AO810 templet.
OSP HOLD 01 through 08
If an OSP TIMEOUT has occurred, will the AO810 hold the last value during OSP?
Enter a YES if it will, or enter a NO if an OSP VALUE will be used.
The Default is NO.
OSP TIMEOUT
Enter the time (msec) after communications is lost, that outputs go to OSP value.
The valid values are:
OFF, 256, 512, and 1024.
296
Appendix A Runtime Templates
3BUR002418-600 A