3.2.3.3

Line/load connection

Table 3- 2
Line/load connection of the Basic Line Module
Terminals
U1, V1, W1
3 AC power input
DCPA, DCNA
Connection for Braking
Module
DCP, DCN
DC power output
PE connection
3.2.3.4

X9 terminal strip

Table 3- 3
X9 terminal strip
Terminal
1
2
3
4
5
6
Max. connectable cross-section 1.5 mm
Chassis power units
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3
Technical specifications
Voltage:
3-ph. 380 V AC -10 % (-15 % < 1 min) to 3-ph. 480 V AC +10 %
3-ph. 500 V AC -10 % (-15 % < 1 min) to 3-ph. 690 V AC +10 %
Frequency: 47 Hz to 63 Hz
Connecting thread:
Frame size FB: M10 / 25 Nm for ring cable lugs to DIN 46234
Frame size GB: M12 / 50 Nm for ring cable lugs to DIN 46234
Voltage:
513 V to 648 V DC
675 V to 932 V DC
Connections:
Frame sizes FB, GB: Threaded bolt M6 / 6 Nm for ring cable lugs to DIN 46234
Voltage:
513 V to 648 V DC
675 V to 932 V DC
Connecting thread:
Frame size FB: M10 / 25 Nm for ring cable lugs to DIN 46234
Frame size GB: M12 / 50 Nm for ring cable lugs to DIN 46234
Connecting thread:
Frame size FB: M10 / 25 Nm for ring cable lugs to DIN 46234
Frame size GB: M12 / 50 Nm for ring cable lugs to DIN 46234
Signal name
P24V
M
Reserved, do not use
Main contactor control
2
Technical specifications
Voltage: 24 V DC (20.4 V – 28.8 V)
Power consumption: max. 1.1 A
240 V AC: max. 8 A
30 V DC: max. 1 A
isolated