Siemens SINAMICS S120 Equipment Manual page 178

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor Modules
4.6 Technical specifications
Table 4- 23
Maximum output frequencies achieved by increasing the pulse frequency
By multiplying the rated pulse frequency with a multiple integer, the following output
frequencies can be achieved taking into account the derating factors in the tables above:
Table 4- 24
1)
178
Derating factor of the output current as a function of the pulse frequency for devices with
a rated pulse frequency of 1.25 kHz
Order no.
Power [kW]
6SL3320-...
1TE36-1AAx
315
1TE37-5AAx
400
1TE38-4AAx
450
1TE41-0AAx
560
1TE41-2AAx
710
1TE41-4AAx
800
1TG28-5AAx
75
1TG31-0AAx
90
1TG31-2AAx
110
1TG31-5AAx
132
1TG31-8AAx
160
1TG32-2AAx
200
1TG32-6AAx
250
1TG33-3AAx
315
1TG34-1AAx
400
1TG34-7AAx
450
1TG35-8AAx
560
1TG37-4AAx
710
1TG38-1AAx
800
1TG38-8AAx
900
1TG41-0AAx
1000
1TG41-3AAx
1200
Maximum output frequencies achieved by increasing the pulse frequency
Pulse frequency
[kHz]
1.25
2
2.5
4
5
The maximum output frequency is limited to 300 Hz due to the closed-loop control.
Output current for a
pulse frequency of 1.25 kHz [A]
Connection voltage 510 – 720 V DC
605
745
840
985
1260
1405
Connection voltage 675 – 1035 V DC
85
100
120
150
175
215
260
330
410
465
575
735
810
910
1025
1270
Derating factor for a
pulse frequency of 2.5 kHz
Maximum output frequency
[Hz]
100
160
200
300
1)
300
1)
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3
72 %
72 %
79 %
87 %
87 %
95 %
89 %
88 %
88 %
84 %
87 %
87 %
88 %
82 %
82 %
87 %
85 %
79 %
95 %
87 %
86 %
79 %
Chassis power units

Advertisement

Table of Contents
loading

Table of Contents