Siemens MICROMASTER 420 Operating Instructions Manual page 92

Canopen option module
Hide thumbs Also See for MICROMASTER 420:
Table of Contents

Advertisement

Information for the CANopen master
Set the number of mapped objects to 2
Write 2 into object 0x1A04 sub 0
T0 00:01:52,9377: 0x603
R0 00:01:54,5864: 0x583
5.7.1.3
Execute the mapping for RPDO 5
Set the number of mapped objects to 0
Write 0 into object 0x1605 sub 0
T0 00:01:54,6741: 0x603
R0 00:01:54,6864: 0x583
The control word is the first mapped object:
Write 0x60400010 into object 0x1605 sub 1
T0 00:01:54,7770: 0x603
R0 00:01:54,7894: 0x583
Modes of operation is the second mapped object:
Write 0x60600008 into object 0x1605 sub 2
T0 00:01:54,8523: 0x603
R0 00:01:54,8659: 0x583
Set the number of mapped objects to 2
Write 2 into object 0x1605 sub 0
T0 00:01:54,9624: 0x603
R0 00:01:56,6833: 0x583
92
8-Data: 2f 04 1a 00 02 00 00 00
8-Data: 60 04 1a 00 00 00 00 00
8-Data: 2f 05 16 00 00 00 00 00
8-Data: 60 05 16 00 00 00 00 00
8-Data: 23 05 16 01 10 00 40 60
8-Data: 60 05 16 01 00 00 00 00
8-Data: 23 05 16 02 08 00 60 60
8-Data: 60 05 16 02 00 00 00 00
8-Data: 2f 05 16 00 02 00 00 00
8-Data: 60 05 16 00 00 00 00 00
CANopen Option Module