The meaning of the bits in control word 2 and status word 2 are as follows:
Table 3-19
Significance of the bits in control word 2 and status word 2
Bit
Control Word 2
Pos.
00
Fixed Frequency Bit 0
01
Fixed Frequency Bit 1
02
Fixed Frequency Bit 2
03
Fixed Frequency Bit 3
(not MICROMASTER 420)
04
Drive data set (DDS) Bit 0
05
Drive data set (DDS) Bit 1
06
Not used
07
Not Used
08
Enable PID
09
Enable DC Brake
10
Not Used
11
Enable Droop
12
Torque Control
(only 440)
13
External Fault
14
Not Used
15
Command Data Set (CDS)
CANopen Option Module
Operating Instructions
6SE6400-5BC00-0BP0
Manually setting
0 = NO
P1020.0 = 2091.0
1 = YES
0 = NO
P1021.0 = 2091.1
1 = YES
0 = NO
P1022.0 = 2091.2
1 = YES
0 = NO
P1023.0 = 2091.3
1 = YES
0 = NO
P0820.0 = 2091.4
1 = YES
0 = NO
P0821.0 = 2091.5
1 = YES
Not Used
Not Used
0 = NO
P2200.0 = 2091.8
1 = YES
0 = NO
P1230.0 = 2091.9
1 = YES
Not Used
0 = NO
Not Used
1 = YES
0 = Speed Control
P1501.0 = 2091.12
1 = Torque Control
0 = NO
P2106.0 = 2091.13
1 = External Fault
Not Used
0 = NO
P0811.0 = 2091.15
1 = YES
Data transfer using CANopen
Status Word 2
DC Brake Active
Act Freq > freq.off
Act Freq > f_min
Act Curr. >= P2170
Act Freq > P2155
Act Freq <= P2155
Act Freq >= setpoint
Act Vdc < P2172
Act Vdc > P2172
Ramping finished
(setpoint reached)
PID output == PID min
PID output == PID max
Not Used
Not Used
Download Data set 0 from
AOP
Download Data set 1 from
AOP
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES
0 = NO
1 = YES