9.5.1

System status message list

Operating errors (code 1000 to 1999)
sorted by code no.
1000 operating error exists
1001 Watchdog
1002 RAM error
1003 Checksum incorrect parameter
1004 Checksum incorrect program
1006 logbook error
1102 ADU error
1104 Undervoltage
1105 Overload
1106 Underload
1107 Legal trade display failure
9.5.2

Technology error message list

Technology error (code 2000 to 4999)
2000 Technology error exists
2001 Timeout tare/set to zero
2002 Trace overload
2003 Set to zero not possible
9.5.3

Data and operating errors message list

Data and operating errors
(code 5000 to 8999)
5000 Data and operating error exists
5001 Command code or data record unknown
5002 Command or data change not possible
because write protection is active
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
Error code
Description and remedy
1000
Group message, at least one operating error exists.
1001
Watchdog, error is displayed for at least 10 seconds. A serious error
has occurred in the function of SIWAREX, e.g. program error, severe
electromagnetic influence on device, etc.
Contact the SIWAREX Support if the error occurs multiple times.
1002
RAM error. An error has occurred in the memory; the memory con-
tent is no longer correct. The module must be switched off. If the
error occurs again, SIWAREX is defective.
1003
Checksum error at parameter. Critical error because the parameters
are no longer safe.
1004
Checksum error program code. Critical error because the program is
no longer safe.
1006
Error when writing/deleting,or logbook full
1102
AD converter error when reading in the measured value. If the error
occurs again, make sure that the EMC recommendations are ob-
served (chapter EMC-compliant setup (Page 25)).
1104
Undervoltage at sensor cables
1105
Overload of scale (ca. 110%)
1106
Underload of scale (ca. -10%)
1107
The SecureDisplay legal trade display no longer communicates with
the module
Error code
Description and remedy
2000
Group message, at least one technology error exists
2001
Taring of scale or set to zero is not possible because a standstill was not
reached during the standstill time. The command was discarded.
2002
The set recording rate for trace function cannot be processed. Set a slow-
er recording rate (chapter "Trace recording cycle (Page 95)")
2003
The switch-on weight is outside the configured value range for set to zero
in data record DR 3 defined by the maximum positive and negative weight.
Error code
Description and remedy
5000
Group error, a bit is set in the data and operating error bits
5001
Command code or data record is not known with current application
5002
The command or changing of data is not possible due to write protec-
tion. The data record was rejected.
Messages
9.5 Message list
135