CHAPTER 10: THEORY OF OPERATION
Phase distance fault type supervision can be enabled/disabled through S
GROUP 1(6) DISTANCE PH DIST PH SELECT SUPV
relays do not employ fault type supervision for the phase distance in all zones.
10.3.3.11 Zero-sequence directional characteristic
The extra zero-sequence characteristic applies to ground zones 2 and higher and is achieved by checking angles between:
•
A ground element — I_0 × Z
•
B ground element — I_0 × Z
•
C ground element — I_0 × Z
The limit angle of the comparator is not adjustable and equals 90°. The zero-sequence directional characteristic improves
directional integrity for time-delayed operations after the memory expires.
10.3.3.12 Overcurrent supervision
The overcurrent supervision responds to the following currents:
•
AB phase element — (I
A
•
BC phase element — (I
B
•
CA phase element — (I
C
•
A, B, C ground element — | 3 × I_0 – 0.05 × I_1 |
The following tables summarize the characteristics of the distance elements.
Table 10-1: Directional mho phase distance functions
Characteristic
Comparator inputs
I × Z – V
Variable mho
I × Z – V
Reactance
I × ZD
Directional
Fault type
NOT SLG
Table 10-2: Directional mho ground distance functions
Characteristic
Comparator inputs
I × Z – V
Variable mho
I × Z – V
Reactance
I_0 × Z
Directional
D
I_2 × Z
Directional
D
Fault-type
I_0
Zero-sequence
I_0 × Z
D
Table 10-3: Directional quadrilateral phase distance functions
Characteristic
Comparator inputs
Reactance
I × Z – V
Directional
I × Z
D
Right Blinder
I × Z
– V
R
Left Blinder
I × Z
– V
L
Fault type
NOT SLG
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
and is applied to phase distance zone 1 to zone 3 only. G60 and L60
and –V_0
D
and –V_0
D
and –V_0
D
– I
) /
B
– I
) /
C
– I
) /
A
V_1M
I × Z
V_1M
See the Fault Type Characteristic section
V_1M
I_0 × Z
V_1M
V_1M
I_2
–V_0
I × Z
V_1M
I × Z
R
I × Z
L
See the Fault Type Characteristic section
ETTINGS GROUPED ELEMENTS SETTING
Limit angle
COMP LIMIT
COMP LIMIT
DIR COMP LIMIT
Removed during open pole conditions
Limit angle
COMP LIMIT
COMP LIMIT
DIR COMP LIMIT
DIR COMP LIMIT (removed when 3I_0 > OC SUPV and I_2 < CUTOFF)
50° (removed during open pole conditions or when 3I_0 > OC SUPV
and I_2 < CUTOFF)
90° (zones 2 and higher only; removed for zones 2 and higher
during open pole conditions)
Limit angle
COMP LIMIT
DIR COMP LIMIT
90°
90°
Removed during open pole conditions
DISTANCE ELEMENTS
10
10-25