FLEXLOGIC
to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.
5.6.5 FlexLogic equation editor
SETTINGS FLEXLOGIC FLEXLOGIC EQUATION EDITOR
FLEXLOGIC
EQUATION EDITOR
There are 1,024 FlexLogic entries available, numbered from 1 to 1024, with default END entry settings. If a "Disabled"
element is selected as a FlexLogic entry, the associated state flag is never set to '1'. Press the +/– key when editing
FlexLogic equations to quickly scan through the major parameter types.
5.6.6 FlexLogic timers
SETTINGS FLEXLOGIC FLEXLOGIC TIMERS FLEXLOGIC TIMER 1(32)
FLEXLOGIC
TIMER 1
5
There are 32 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
— Selects the time measurement unit.
TIMER 1 TYPE
TIMER 1 PICKUP DELAY
TIMER 1 DROPOUT DELAY
5.6.7 FlexElements
SETTINGS FLEXLOGIC FLEXELEMENTS FLEXELEMENT 1(8)
FLEXELEMENT 1
5-190
FLEXLOGIC ENTRY 1:
END
FLEXLOGIC ENTRY 1024:
END
TIMER 1
TYPE: millisecond
TIMER 1 PICKUP
DELAY:
0
TIMER 1 DROPOUT
DELAY:
0
— Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
— Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."
FLEXELEMENT 1
FUNCTION: Disabled
FLEXELEMENT 1 NAME:
FxE 1
FLEXELEMENT 1 +IN:
Off
FLEXELEMENT 1 -IN:
Off
FLEXELEMENT 1 INPUT
MODE: SIGNED
FLEXELEMENT 1 COMP
MODE: LEVEL
FLEXELEMENT 1
DIRECTION: OVER
Range: FlexLogic operands
Range: FlexLogic operands
Range: millisecond, second, minute
Range: 0 to 60000 in steps of 1
Range: 0 to 60000 in steps of 1
Range: Disabled, Enabled
Range: up to six alphanumeric characters
Range: Off, any analog actual value parameter
Range: Off, any analog actual value parameter
Range: SIGNED, ABSOLUTE
Range: LEVEL, DELTA
Range: OVER, UNDER
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS