CHAPTER 5: SETTINGS
Value (decimal)
Number of ASDUs
13
3
14
4
5.5.8.8 Settings
The PMU settings are organized as follows.
SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PHASOR MEASUREMENT UNIT 1
PHASOR MEASUREMENT
UNIT 1
5.5.8.9 Basic configuration
SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT BASIC CONFIGURATION PMU 1
PMU 1 BASIC
CONFIGURATION
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PMU 1 BASIC
CONFIGURATION
PMU 1
CALIBRATION
PMU 1
TRIGGERING
PMU 1
RECORDING
PMU 1
FUNCTION: Disabled
PMU 1 IDCODE:
1
PMU 1 STN:
GE-UR-PMU
PMU 1 SIGNAL SOURCE:
SRC 1
PMU 1 CLASS:
M-CLASS
PMU 1 FORMAT:
Integer
PMU 1 STYLE:
Polar
PMU 1 RATE:
10/sec
PMU 1 f & df/dt
FILTER: None
C37.118 PMU 1
CONFIGURATION
PMU 1 PHS- 1:
Off
PMU 1 PHS-14:
Off
PMU 1 PHS- 1:
NM: GE-UR-PMU-PHS 1
PMU 1 PHS-14:
NM: GE-UR-PMU-PHS 14
See below
See page 5-156
See page 5-158
See page 5-164
Range:
Enabled, Disabled
Range:
1 to 65534 in steps of 1
Range:
32-character ASCII string truncated to 16
characters if mapped into C37.118 Default: GE-UR-PMU
Range:
available signal sources
Range:
None, M-CLASS, P-CLASS
Range:
Integer, Floating-point
Range:
Polar, Rectangular
Range: 1, 2, 4, 5, 10, 12, 15,20, 25, 30,50, 60, 100, 120
/sec
Range: None, 10Hz/s <10Hz, 10Hz/s <20Hz, 20Hz/s
<10Hz, 20Hz/s <20Hz
See below
Range:
available synchrophasor values
Range:
available synchrophasor values
Range:
16-character ASCII string
Range:
16-character ASCII string
SYSTEM SETUP
5
5-153