58 Planning the electrical installation
Q1
Main switch for the drive
Q4
Bypass circuit breaker
K1
Drive main contactor
K4
Bypass contactor
K5
Drive output contactor

Switching the motor power supply from drive to direct-on-line

1. Stop the drive and the motor with the drive control panel (drive in local control mode)
or with the external stop signal (drive in remote control mode).
2. Open the main contactor of the drive with S11.
3. Switch the motor power supply from the drive to direct-on-line with S40.
4. Wait for 10 seconds to allow the motor magnetization to die away.
5. Start the motor with S41.
S11
Drive main contactor on/off control
S40
Motor power supply selection (drive or direct-on-
line)
S41
Start when the motor is connected direct-on-line
S42
Stop when the motor is connected direct-on-line
U1
Drive

Hide quick links: