Addr.
_:9901:108
_:9901:116
_:9901:112
Trigger Qsum 1
_:9961:1
_:9961:111
_:9961:101
_:9961:105
_:9961:113
_:9961:102
_:9961:106
_:9961:114
_:9961:103
_:9961:107
_:9961:115
_:9961:104
_:9961:108
_:9961:116
_:9961:112
Trigger Ssum 1
_:10021:1
_:10021:101
_:10021:105
_:10021:113
_:10021:102
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Parameter
C
Trigger Psum 1:dM/dt
1 A @ 100 Irated 0.36 Wto 6000.00 W
drop (/Filter time)
5 A @ 100 Irated 1.80 W to 300000.00 W
Trigger Psum 1:dM/dt
drop hysteresis
Trigger Psum 1:Filter
time
Trigger Qsum 1:Mode
Trigger Qsum 1:Power
direction
Trigger Qsum 1:Max.
trigger active
Trigger Qsum 1:Max.
1 A @ 100 Irated 0.36 var to 60000.00 var
trigger
5 A @ 100 Irated 1.80 var to 300000.00 var
Trigger Qsum 1:Max.
trigger hysteresis
Trigger Qsum 1:Min.
trigger active
Trigger Qsum 1:Min.
1 A @ 100 Irated 0.36 var to 60000.00 var
trigger
5 A @ 100 Irated 1.80 var to 300000.00 var
Trigger Qsum 1:Min.
trigger hysteresis
Trigger Qsum 1:dM/dt
rise active
Trigger Qsum 1:dM/dt
1 A @ 100 Irated 0.36 var to 60000.00 var
rise (/Filter time)
5 A @ 100 Irated 1.80 var to 300000.00 var
Trigger Qsum 1:dM/dt
rise hysteresis
Trigger Qsum 1:dM/dt
drop active
Trigger Qsum 1:dM/dt
1 A @ 100 Irated 0.36 var to 60000.00 var
drop (/Filter time)
5 A @ 100 Irated 1.80 var to 300000.00 var
Trigger Qsum 1:dM/dt
drop hysteresis
Trigger Qsum 1:Filter
time
Trigger Ssum 1:Mode
Trigger Ssum 1:Max.
trigger active
Trigger Ssum 1:Max.
1 A @ 100 Irated 0.36 VA to 60000.00 VA
trigger
5 A @ 100 Irated 1.80 VA to 300000.00 VA
Trigger Ssum 1:Max.
trigger hysteresis
Trigger Ssum 1:Min.
trigger active
7.5 Trigger Functions 3-Phase
Setting Options
0.900 p.u. to 0.990 p.u.
2cyclesto250 cycles
•
off
•
on
•
test
•
negative
•
positive
•
no
•
yes
0.900 p.u. to 0.990 p.u.
•
no
•
yes
1.010 p.u. to 1.100 p.u.
•
no
•
yes
0.900 p.u. to 0.990 p.u.
•
no
•
yes
0.900 p.u. to 0.990 p.u.
2cyclesto250 cycles
•
off
•
on
•
test
•
no
•
yes
0.900 p.u. to 0.990 p.u.
•
no
•
yes
Fault Recorder
Default Setting
34.64 W
173.21 W
0.980 p.u.
2 cycles
off
positive
yes
207.85 var
1039.23 var
0.980 p.u.
yes
138.56 var
692.82 var
1.020 p.u.
no
34.64 var
173.21 var
0.980 p.u.
no
34.64 var
173.21 var
0.980 p.u.
2 cycles
off
yes
207.85 VA
1039.23 VA
0.980 p.u.
yes
345