Settings - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Fault Recorder
7.4 Trigger Functions 1-Phase
The hysteresis is preset at the factory to 1.020 p.u. (equal to 2 %) of the parameter Min. trigger and can
be adjusted.
Parameter: dM/dt Rise Active - dM/dt Rise (/Filter Time) - dM/dt Rise Hysteresis - Filter Time
Default setting (_:19441:103) dM/dt rise active = no
Default setting (_:19441:107) dM/dt rise (/Filter time) = 0 var
Default setting (_:19441:115) dM/dt rise hysteresis = 0.980 p.u.
Default setting (_:19441:112) Filter time = 2 periods
With the dM/dt rise active parameter, you activate the gradient trigger in order to monitor the positive
gradients of the sum reactive power using the set filtering time (input in periods).
Parameter Value
yes
no
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter dM/dt rise (/Filter
time) and can be adjusted.
Parameter: dM/dt Drop Active - dM/dt Drop (/Filter Time) - dM/dt Drop Hysteresis - Filter Time
Default setting (_:19441:104) dM/dt drop active = no
Default setting (_:19441:108) dM/dt drop (/Filter time) = 0 var
Default setting (_:19441:116) dM/dt drop hysteresis = 0.980 p.u.
Default setting (_:19441:112) Filter time = 2 periods
With the dM/dt drop active parameter, you activate the gradient trigger in order to monitor the negative
gradients of the sum reactive power using the set filtering time (input in periods).
Parameter Value
yes
no
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter dM/dt drop (/Filter
time) and can be adjusted.
7.4.4.6

Settings

Addr.
Trigger P 1
_:19411:1
_:19411:111
_:19411:101
_:19411:105
_:19411:113
_:19411:102
294
Description
The positive gradient of the sum reactive power is monitored.
The positive gradient of the sum reactive power is not monitored.
Description
The negative gradient of the sum reactive power is monitored.
The negative gradient of the sum reactive power is not monitored.
Parameter
C
Trigger P 1:Mode
Trigger P 1:Power direc-
tion
Trigger P 1:Max. trigger
active
Trigger P 1:Max. trigger
1 A @ 100 Irated 0.20 W to 20000.00 W
5 A @ 100 Irated 0.60 W to 100000.00 W
Trigger P 1:Max. trigger
hysteresis
Trigger P 1:Min. trigger
active
Setting Options
off
on
test
negative
positive
no
yes
0.900 p.u. to 0.990 p.u.
no
yes
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Default Setting
off
positive
yes
120.00 W
600.00 W
0.980 p.u.
yes