Settings - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Parameter: Flash-Memory Size
Recommended setting value (_:10111:161) Flash-memory size = 1000 MB
With the parameter Flash-memory size you specify a maximum memory capacity of the continuous
recorder on the mass storage.
If the flash memory becomes full while recording new fault records, the device automatically deletes the
oldest data in order to continue recording (ring buffer).
The record time is limited by the set flash memory size, number of routed tracks and by the averaging time.
NOTE
i
i
If you change the capacity of the recorder or delete a recorder instance, the flash memory of the device is
re-organized and all recordings of the device – not just those of the changed recorder – are automatically
and irrevocably deleted.
Before this, save your recordings by exporting them manually in DIGSI 5 or archiving them in SICAM PQS.
Then, delete your recordings in DIGSI 5 to avoid inconsistencies between new and old recordings.
NOTE
i
i
The setting aid Estimated record time is dimmed and thus, you cannot set or change it.
NOTE
i
i
Due to the internal administration data, the complete flash memory size for the storing of recordings is not
available. The Estimated record time provides user information that helps to estimate how many
recordings can be stored in the reserved flash memory. The actual size of a continuous record depends on
the degree of compression and the number of stored events.
Parameter: Averaging Time
Recommended setting value (_:10111:112) Averaging time = 600 s
With the parameter Averaging time, you determine the time range over which an average value is formed
and stored in the memory.
The average value is always formed over the entire averaging time.
NOTE
i
i
The angles are not determined but rather used at the end of the averaging time with the current value.
7.2.8.5

Settings

Addr.
General
_:2731:1
Control
_:10111:161
_:10111:102
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Parameter
C
General:Mode
Continuous 1:Flash-
memory size
Continuous 1:Estimated
record time
7.2 Function-Group Type Recorder
Setting Options
off
on
0.200 GB to 14.800 GB
0.0 day(s) to 214748364.7
day(s)
Fault Recorder
Default Setting
on
1.000 GB
0.0 day(s)
249