Advertisement

Fault Recorder
7.5 Trigger Functions 3-Phase
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter Max. trigger and can
be adjusted.
Parameter: dM/dt Rise Active - dM/dt Rise (/Filter Time) - dM/dt Rise Hysteresis - Filter Time
Default setting (_:9691:103) dM/dt rise active = no
Default setting (_:9691:107) dM/dt rise (/Filter time) = 11.547 V
Default setting (_:9691:115) dM/dt rise hysteresis = 0.980 p.u.
Default setting (_:9691:112) Filter time = 2 periods
With the dM/dt rise active parameter, you activate the gradient trigger in order to monitor the positive
gradients of the voltage in the negative-sequence system using the set filtering time (input in periods).
Parameter Value
yes
no
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter dM/dt rise (/Filter
time) and can be adjusted.
7.5.1.9

Settings

Addr.
General
_:9571:1
_:9571:9
_:9571:117
_:9571:112
Max. trigger
_:9571:101
_:9571:105
_:9571:118
_:9571:119
_:9571:120
_:9571:113
Min. trigger
_:9571:102
_:9571:106
_:9571:121
308
Description
The positive gradient of the voltage in the negative-sequence system is
monitored.
The positive gradient of the voltage in the negative-sequence system is not
monitored.
Parameter
C
Trig. V fund 1:Mode
Trig. V fund 1:Measured
value
Trig. V fund 1:Phase-
selective
Trig. V fund 1:Filter time
Trig. V fund 1:Max.
active
Trig. V fund 1:Max.
(Non-phs sel.)
Trig. V fund 1:Max. phs
A(AB)
Trig. V fund 1:Max. phs
B(BC)
Trig. V fund 1:Max. phs
C(CA)
Trig. V fund 1:Max.
hysteresis
Trig. V fund 1:Min. active
Trig. V fund 1:Min. (Non-
phs sel.)
Trig. V fund 1:Min. phs
A(AB)
Setting Options
off
on
test
phase-to-ground
phase-to-phase
no
yes
2 cycles to 250 cycles
no
yes
0.300 V to 340.000 V
0.300 V to 340.000 V
0.300 V to 340.000 V
0.300 V to 340.000 V
0.900 p.u. to 0.990 p.u.
no
yes
0.300 V to 340.000 V
0.300 V to 340.000 V
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Default Setting
off
phase-to-phase
no
2 cycles
yes
120.000 V
120.000 V
120.000 V
120.000 V
0.980 p.u.
yes
80.000 V
80.000 V