GE M-Pact Plus Operating & Installation Instructions Manual page 24

Air circuit breakers
Hide thumbs Also See for M-Pact Plus:
Table of Contents

Advertisement

BREAKER
6.7.3
Holding undervoltage release coil in one hand tilt the unit forward, engage
front hooks into top support plate.
6.7.4
Tilt backwards until the rear hooks engage in the slots and press down into
position.
6.7.5
Fix external resistor unit in place with the 2 off M5 screws and shake proof
washers provided.
6.7.6
Connect undervoltage release coil flying leads into low-tension auxiliary
isolating contact terminals B15 and B16 as per schematic diagram, observing
polarity markings on DC versions.
6.7.7
The front facia must now be placed in the reverse order to the removal.
6.7.8
The undervoltage release coil is now is fitted and ready for testing.
6.7.3Die Unterspannungsauslöserspule nach vorne geneigt in einer Hand haltend
in die vorderen Befestigungsschlitze einführen.
6.7.4
Nun die Spule nach hinten drehen bis die Schnapphaken greifen.
6.7.5
Die externe Elektronik mit zwei M5 Schrauben nebst Vibrationsschutz
Scheiben anbringen.
6.7.6
Danach den Unterspannungsauslöser elektrisch an Klemmblock B15 und
B 16 anschließen. Auf Polung für DC Variante achten.
6.7.7
Den Deckel und den Handspannhebel wieder anbauen.
6.7.8
Jetzt ist der Arbeitsstromauslöser bereit um eine Funktionsprüfung
durchzuführen.