Weight and Dimension
Weight and Dimension
Weight and Dimension
Weight and Dimension
Weight and Dimension
Weights (Kg)
Fixed pattern ACB
400 to1600A
2000 to 2500A
800 to 3200A
4000A
Withdrawable ACB
400 to1600A
2000 to 2500A
800 to 3200A
4000A
Casette only
400 to1600A
2000 to 2500A
800 to 3200A
4000A
Dimensions in mm
Frame size
1
2
2
(1) Height (H) is from mounting surface to highest part of the M-PACT Plus
(2) Depth (D) is from the cubicle door to the rear moulding
3) Length (L) is distance between widest part of the breaker
W - Withdrawable
F - Fixed
S range
Frame
3 Pole
4 Pole
1
36
44
1
43
54
2
53
68
2
53
68
Frame
3 Pole
4 Pole
1
63
77
1
72
90
2
90
117
2
111
144
Frame
3 Pole
4 Pole
1
27
33
1
29
36
2
37
49
2
58
76
Rating (A)
Poles
400 to 2500
3
4
800 to 3200
3
4
4000
3
4
N range
3 Pole
4 Pole
39
49
43
54
53
68
53
68
3 Pole
4 Pole
68
84
72
90
90
117
111
144
3 Pole
4 Pole
29
36
29
36
37
49
58
76
Type
Height (1)
W
440
F
430
W
440
F
430
W
440
F
430
W
440
F
430
W
440
F
430
W
440
F
430
H
110
H range
3 Pole
4 Pole
N/A
N/A
N/A
N/A
53
68
53
68
3 Pole
4 Pole
N/A
N/A
N/A
N/A
90
117
111
144
3 Pole
4 Pole
N/A
N/A
N/A
N/A
37
49
58
76
Length (3)
Depth (2)
329
390
329
328
429
390
429
328
419
392
419
328
549
392
549
328
419
482
419
328
549
482
549
328
D
L