ABB i-bus KNX Product Manual page 70

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable Group object "Flexible time
for dimming/fade time ..."
Options:
Linked group object:
This group object changes various dimming times via the KNX. It can affect various ballasts, groups and
the output. Whether the ballast, group or output evaluates this group object is defined in the corresponding
ballast, group or output. This group object can influence the following functions.
Note
To use the Flexible dimming time function you first need to enable the output's Flexible time for
dimming/fade time group object in the A Output parameter window. You also need to select the function
for the parameter that can be changed via KNX. We recommend that you only change one time via
KNX. Otherwise the dimming time has to be rewritten on the ballast every time a function is called,
which impairs function performance.
Yes: The Flexible time for dimming/fade time ... group object is enabled. It can be used to change the
dimming time for various functions.
No: The group object is not enabled.
68 2CDC507164D0201 | DG/S x.64.1.1
Yes
No
Dimming time for turn on/off value
Dimming time for brightness value
Dimming time for slave brightness value
Scene transition time
Selection of Yes option:
Dependent parameters:
Object format of flexible time for
dimming/fade time
Options:
DALI format (1...15)
KNX format time 100 ms
KNX format time 1 s
Linked group object:
Flexible time for dimming/fade time ...
Dimming/fade time (DALI format (0...15))
Dimming/fade time (time 100 ms)
Dimming/fade time (time 1 s)

Advertisement

Table of Contents
loading

Table of Contents