ABB i-bus KNX Product Manual page 219

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Planning and application
The following table shows how the reaction when the Staircase lighting function is parametrized.
Operating situation
or
Group objects
Download (start)
Download (end)
voltage failure
KNX bus
voltage
recovery
voltage failure
DALI
or
Gateway
supply
ballast recovery
ON
Switch
OFF
Relative dimming
Set Brightness Value
Recall scene
0
Activate Staircase
lighting function
1
ON
Forced
operation/Block
OFF
ON
Partial failure
OFF
Inactive
Standby
(turn off brightness)
- Mode: Group x/Ballast x Staircase lighting – Inactive/Standby/Active and on/State before failure
- Group x/Ballast x Fault – Min/Max/OFF/No change/State before failure
- Group x/Ballast x Fault – Min/Max/OFF/No change/Actual KNX target state
→ Active and
starts
 S taircase
Switch-on value
lighting
OFF
(turn off brightness)
(turn off brightness)
Dimming,
Dimming
remains in standby
Brightness value,
Brightness value
remains in standby
Scene
Scene
→ goes to inactive
No reaction
Group x/Ballast x staircase lighting - Activate and ON/Activated standby
Forced brightness set. Forced operation has the highest priority.
Actual KNX target
state set
Partial failure value set. Partial failure takes priority over additional function.
Actual KNX target
state set
Staircase lighting function
Dimming-up
time
Such as KNX bus voltage failure
Such as KNX bus voltage recovery
Parametrizable brightness value – ballast: fault is set.
Staircase lighting function is discontinued.
Parametrizable:
Parametrizable:
Group x/Ballast x Fault – Min/Max/OFF/No change
Staircase lighting function is discontinued
Parametrizable:
No reaction
OFF
Dimming-down time starts
Group x/Ballast x Staircase lighting – No reaction/Dimming standby
Group x/Ballast x Staircase lighting – No reaction/Brightness value
Group x/Ballast x Staircase lighting – No reaction/Scene and standby
→ goes to inactive, brightness value is retained
Parametrizable:
Staircase lighting active at basic brightness
Staircase lighting active at basic brightness
Active
Dimming-down time
Staircase lighting
time
Basic brightness
Staircase lighting time
Staircase lighting

will be restarted
No reaction if basic
brightness runtime
unlimited, otherwise OFF
(Turn off brightness)
Parametrizable:
Parametrizable:
standby
Parametrizable:
DG/S x.64.1.1 | 2CDC507164D0201 217
Run time
is restarted

Advertisement

Table of Contents
loading

Table of Contents