ABB i-bus KNX Product Manual page 207

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
56, 67...
232, 243...
This group object is enabled if the Enable Lamp burn-in function object "Burn-in lamps" parameter is set to Yes in the
X Functions template (group x/ballast x) (Forced operation/Block/Burn-in/Partial failure), p. 102.
The Burn-in lamp group object is used to burn in group devices or individual ballasts (lamps).
Burn-in is initiated by a telegram with the value 1. The group or ballast can only be controlled at 0% (OFF) or 100% brightness.
After the burn-in time has elapsed, the group/ballast can be dimmed as usual and the programmed light scenes can be
recalled. As DALI value simulation continues to run in the background during burn-in, the actual brightness value is
automatically set when burn-in ends.
If another telegram with the value 1 is received on the Burn-in lamps group object during the burn-in time, the time restarts
from the beginning.
A telegram with the value 0 deactivates the Burn-in function and enables "normal" operation. The burn-in time is only counted
if a ballast is connected to the DALI output and has a supply voltage. The burn-in time counts in five minute steps.
The burn-in time is not lost in the event of KNX bus voltage failure, light controller supply voltage failure or download.
Telegram value:
56, 67...
232, 243...
This group object is enabled if the Enable Lamp burn-in function object "Burn-in lamps" parameter and Status of burn-in
subparameter are set to Yes in X Functions template (group x/ballast x) (Forced operation/Block/Burn-in/Partial failure),
p. 102.
The Burn-in lamps/Status group object now has two properties:
Telegram value:
You can define whether the status is sent On change and/or On request.
Function
Burn-in lamp
Dependent on parameter
1 = Activate Burn-in function
0 = Deactivate Burn-in function
Note
Alternatively, the burn-in of all the groups and ballasts on the DALI output can be triggered via the Burn-in
lamps/Status group object (no. 34) for the DALI output. The Burn-in lamps/status group objects for the DALI output
and group x or ballast x are mutually independent. The group burn-in time is triggered by a telegram with the value 1
or reset with the value 0. This is independent of whether the telegram is received via the group x, ballast x or DALI
output group object.
Burn-in lamps/status
Dependent on parameter
First, the Burn-in function can be individually activated for the group or for single ballasts (lamps) (for a description see the
previous group object, Burn-in lamp).
Second, the object transmits the burn-in status on the KNX.
1 = Burn-in function active
0 = Burn-in function not active
Group object name
Output A - Group x
Output A - Ballast x
Enable Lamp burn-in function object "Burn-in lamps"
Output A - Group x
Output A - Ballast x
Status of burn-in
DG/S x.64.1.1 | 2CDC507164D0201 205
Data type
Flags
1 bit
C, R, W, T
DPT 1.010
1 bit
C, R, W, T
DPT 1.010