Commissioning
3.3.2

Group objects General

No.
1
This group object is enabled if the Enable Group object "In operation" parameter is set to Yes in the General parameter
window, p.28.
In order to regularly monitor the presence of the device on the KNX, an In operation monitoring telegram can be sent cyclically
on the bus.
As long as the group object is activated, it sends a parametrizable In operation telegram.
2
This group object disables manual operation.
When manual operation is disabled, connected DALI devices cannot be manually switched via the DALI gateway. Activating
the Trigger DALI addressing function by pressing and holding the
However, the status of manual operation – disabled (1) and enabled (0) – can be queried and/or sent via KNX with this group
object.
Telegram value:
3
This group object is enabled if the Enable Group object "Gateway supply voltage fault" parameter is set to Yes in the General
parameter window, p. 28.
If the gateway supply voltage fails for more than five seconds, a Fault message telegram is sent immediately.
The time depends on the DALI load: it is < 5 seconds when idling and < 1 second at full load.
Telegram value:
4
This group object is enabled if the Enable acknowledgement via object "Acknowledge gateway supply voltage fault" parameter
is set to Yes in the General parameter window, p. 28.
This group object is used to reset the Gateway supply voltage fault. The fault is only reset after acknowledgement if it has
been corrected.
Telegram value:
Function
In operation
Dependent on parameter
Disable manual operation/Status
Dependent on parameter
0 = manual operation/
1 = manual operation/
Gateway supply voltage fault
Dependent on parameter
0 = No fault
1 = Fault
Acknowledge gateway supply voltage
fault
Dependent on parameter
0 = No function
1 = Reset fault messages
Group object name
General
Enable Group object "In operation"
General
Enable manual operation.
Obj "Disable manual operation/Status"
push button (> 5 s) is also disabled.
push button is enabled.
push button is disabled.
General
Enable Group object
"Gateway supply voltage fault"
General
Enable acknowledgement via object
"Acknowledge gateway supply
voltage fault"
Data type
Flags
1 bit
C, R, T
DPT 1.002
1 bit
C, R, W, T
DPT 1.003
1 bit
C, R, T
DPT 1.005
1 bit
C, W
DPT 1.015
DG/S x.64.1.1 | 2CDC507164D0201 175