ABB i-bus
KNX
Commissioning
Enable Group object
"Disable fault messages/Status"
Options:
Linked group object:
This parameter enables the Disable fault messages/Status group object. At the same time, it makes the
Disable fault messages function available. When messages are disabled, the faults are evaluated but not
sent on the KNX. Nor are the values of the group objects updated.
The Disable fault messages/Status group object not only activates and deactivates the function but also
sends or reads its status.
Disabling fault messages minimizes system latency by reducing the KNX load.
When fault messages are enabled, all faults are sent in accordance with their parametrization. If a fault still
exists after fault messages are enabled, this fault is recorded and the information is sent on the KNX in
accordance with the parametrization.
Yes: The Disable fault messages function and group object are enabled.
No: The Disable fault messages function and group object are not enabled.
Yes
No
Disable fault messages/Status
DG/S x.64.1.1 | 2CDC507164D0201 59