Procedure
To perform pretuning, follow these steps:
1. Double-click the "PID_Compact > Commissioning" entry in the project tree.
2. Select the entry "Pretuning" in the "Tuning mode" drop-down list.
3. Click the "Start" icon.
– An online connection will be established.
– Value recording is started.
– Pretuning is started.
– The "Status" field displays the current steps and any errors that may have occurred.
Result
If pretuning was performed without an error message, the PID parameters have been tuned.
PID_Compact switches to automatic mode and uses the tuned parameters. The tuned PID
parameters will be retained during power OFF and a restart of the CPU.
If pretuning is not possible, PID_Compact responds with the configured reaction to errors.
See also
Parameters State and Mode V2 (Page 265)
PID control
Function Manual, 03/2017, A5E35300227-AC
The progress bar indicates the progress of the current step.
Note
Click the "Stop" icon when the progress bar has reached 100% and it can be assumed
the controller tuning function is blocked. Check the configuration of the technology
object and, if necessary, restart controller tuning.
Using PID_Compact
4.2 PID_Compact V2