9.2 PID_3Step
9.2.4.4

Input parameters of PID_3Step V2

Table 9- 7
Input parameters of PID_3Step V2
Parameter
Setpoint
Input
Input_PER
Actuator_H
Actuator_L
Feedback
Feedback_PER
Disturbance
ManualEnable
ManualValue
316
Data type
Default
REAL
0.0
REAL
0.0
INT
0
BOOL
FALSE
BOOL
FALSE
REAL
0.0
INT
0
REAL
0.0
BOOL
FALSE
REAL
0.0
Description
Setpoint of the PID controller in automatic mode
A tag of the user program is used as source for the process
value.
If you are using parameter Input, then Con-
fig.InputPerOn = FALSE must be set.
An analog input is used as the source of the process value.
If you are using parameter Input_PER, then Con-
fig.InputPerOn = TRUE must be set.
Digital position feedback of the valve for the high endstop
If Actuator_H = TRUE, the valve is at the high endstop and is
no longer moved towards this direction.
Digital position feedback of the valve for the low endstop
If Actuator_L = TRUE, the valve is at the low endstop and is
no longer moved towards this direction.
Position feedback of the valve
If you are using parameter Feedback, then Con-
fig.FeedbackPerOn = FALSE must be set.
Analog position feedback of a valve
If you are using parameter Feedback_PER, then Con-
fig.FeedbackPerOn = TRUE must be set.
Feedback_PER is scaled based on the tags:
Config.FeedbackScaling.LowerPointIn
Config.FeedbackScaling.UpperPointIn
Config.FeedbackScaling.LowerPointOut
Config.FeedbackScaling.UpperPointOut
Disturbance variable or precontrol value
A FALSE -> TRUE edge activates "manual mode", while
State = 4, Mode remains unchanged.
As long as ManualEnable = TRUE, you cannot change the
operating mode via a rising edge at ModeActivate or use
the commissioning dialog.
A TRUE -> FALSE edge activates the operating mode that
is specified by Mode.
We recommend that you change the operating mode using
ModeActivate only.
In manual mode, the absolute position of the valve is speci-
fied. ManualValue is only evaluated if you are using Out-
put_PER, or if position feedback is available.
Function Manual, 03/2017, A5E35300227-AC