Output Parameters Cont_C - Siemens SIMATIC S7-1200 Function Manual

Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Instructions
9.4 PID basic functions
Parameters
Data
type
LMN_HLM
REAL
LMN_LLM
REAL
PV_FAC
REAL
PV_OFF
REAL
LMN_FAC
REAL
LMN_OFF
REAL
I_ITLVAL
REAL
DISV
REAL
1) Parameters in the setpoint and process value branches with the same unit
2) Parameters in the manipulated value branch with the same unit
9.4.1.5

Output parameters CONT_C

Table 9- 14
Output parameters CONT_C
Parameter
Data
type
LMN
REAL
LMN_PER
WORD
QLMN_HLM
BOOL
QLMN_LLM
BOOL
LMN_P
REAL
LMN_I
REAL
LMN_D
REAL
PV
REAL
ER
REAL
454
Default
Description
100.0
The manipulated value is always restricted to a high limit and low limit. The "High
limit of manipulated value" input specifies the high limit.
Permissible are real values starting at LMN_LLM or a physical variable 2).
0.0
The manipulated value is always restricted to a high limit and low limit. The "Low
limit of manipulated value" input specifies the low limit.
Permissible are real values up to LMN_HLM or a physical variable 2).
1.0
The "Process value factor" input is multiplied by the process value. The input is
used to scale the process value range.
0.0
The input "Process value offset" is added to the process value. The input is used to
scale the process value range.
1.0
The "Manipulated value factor" input is multiplied with the manipulated value. The
input is used to scale the manipulated value range.
0.0
The input "Manipulated value offset" is added to the process value. The input is
used to scale the manipulated value range.
0.0
The output of the integral action can be set at the I_ITL_ON input. The initialization
value is 
 a pplied to the input "Initialization value of 
 t he I-action."
Permissible are values of -100.0 to 100.0 (%) or a physical variable 2).
0.0
For feedforward control, the disturbance variable is interconnected to the "Disturb-
ance variable" input.
Permissible are values of -100.0 to 100.0 (%) or a physical variable 2).
Default
Description
0.0
The effective "Manipulated value" is output in 
 f loating point format at the "Manipu-
lated 
 v alue" output.
W#16#000
The manipulated value in I/O format is interconnected on the input "Manipulated
0
value I/O" with the controller.
FALSE
The manipulated value is always restricted to a high limit and low limit. The output
"High 
 l imit of manipulated value reached" 
 i ndicates that the high limit has been

 r eached.
FALSE
The manipulated value is always restricted to a high limit and low limit. The output
"Low 
 l imit of manipulated value reached" 
 i ndicates that the low limit has been

 r eached.
0.0
The "P-action" output contains the proportional action of the manipulated variable.
0.0
The "I-action" output contains the integral action of the manipulated variable.
0.0
The "D-action" output contains the derivative action of the manipulated variable.
0.0
The effective process value is output at the "Process value" output.
0.0
The effective system deviation is output at the "Error signal" output.
Function Manual, 03/2017, A5E35300227-AC