9.4 PID basic functions
Parameters
Address Data type
CON_ZONE
182.0
CONZ_ON
186.0
TUN_ON
186.1
TUN_ST
186.2
UNDO_PAR
186.3
SAVE_PAR
186.4
LOAD_PID
186.5
PID_ON
186.6
GAIN_P
188.0
TU
192.0
TA
196.0
KIG
200.0
N_PTN
204.0
TM_LAG_P
208.0
T_P_INF
212.0
P_INF
216.0
LMN0
220.0
PV0
224.0
492
Default
Description
REAL
100.0
If the control deviation is greater than the control zone band, the high
output value limit is output as output value.
If the control deviation is less than the negative control zone band, the
low output value limit is output as the output value.
The valid values depend on the sensors used.
BOOL
FALSE
You can use CONZ_ON =TRUE to enable the control zone.
BOOL
FALSE
If TUN_ON=TRUE, the output value is averaged until the output value
excitation TUN_DLMN is enabled either by a setpoint step-change or by
TUN_ST=TRUE.
BOOL
FALSE
If the setpoint is to remain constant during controller tuning at the oper-
ating point, a output value step-change by the amount of TUN_DLMN is
activated by TUN_ST=1.
BOOL
FALSE
Loads the controller parametersPFAC_SP, GAIN, TI, TD,
D_FCONZ_ON and CON_ZONE from the data structure PAR_SAVE
(only in manual mode).
BOOL
FALSE
Saves the controller parameters PFAC_SP, GAIN, TI, TD, D_F,
CONZ_ON and CON_ZONE in the data structure PAR_SAVE.
BOOL
FALSE
Loads the controller parametersGAIN, TI,TD depending on PID_ON
from the data structure PI_CON or PID_CON (only in manual mode)
BOOL
TRUE
At the PID_ON input, you can specify whether or not the tuned control-
ler will operate as a PI or PID controller.
With certain process types it is nevertheless possible that only a PI
controller will be designed despite PID_ON = TRUE.
REAL
0.0
Identified process gain. In the case of process type I, GAIN_P tends to
be estimated too low.
REAL
0.0
Identified time lag of the process.
TU ≥ 3*CYCLE
REAL
0.0
Identified recovery time of the process. In the case of process type I, TA
tends to be estimated too low.
REAL
0.0
Maximum process value rise at manipulated tag excitation from
0 to 100 % [1/s]
GAIN_P = 0.01 * KIG * TA
REAL
0.0
The parameter specifies the order of the process. "Non-integer values"
are also possible.
Values from 1.01 to 10.0 are permitted.
REAL
0.0
Time constants of a PTN model (practical values only for N_PTN >= 2).
REAL
0.0
Time from process excitation until the point of inflection.
REAL
0.0
Process value change from process excitation until the point of inflec-
tion.
The valid values depend on the sensors used.
REAL
0.0
Output value at the start of tuning
Detected in phase 1 (mean value).
Values from 0 to 100 % are permitted.
REAL
0.0
Process value at the start of tuning
PID controller: PID_ON = TRUE
PI controller: PID_ON = FALSE
Function Manual, 03/2017, A5E35300227-AC