9.4 PID basic functions
9.4.4.7

In/out parameters TCONT_CP

Table 9- 21
In/out parameters TCONT_CP
Parameters
Address
CYCLE
26.0
CYCLE_P
30.0
SP_INT
34.0
MAN
38.0
COM_RST
42.0
MAN_ON
42.1
See also
Operating principle of the pulse generator (Page 481)
Block diagram TCONT_CP (Page 484)
488
Data
Default
Description
type
REAL
0.1 s
Sets the sampling time for the PID algorithm. In phase 1, the tuner calcu-
lates
the sampling time and enters it in CYCLE.
CYCLE > 0.001 s
REAL
0.02 s
At this input, you set the sampling time for the pulse shaper action. In
phase 1, the TCONT_CP instruction calculates the sampling time and
enters it in CYCLE_P.
CYCLE_P > 0.001 s
REAL
0.0
The input "Internal setpoint" is used to specify a setpoint.
The valid values depend on the sensors used.
REAL
0.0
The "Manual value" input is used to set a manual value. In automatic
mode, it tracks the manipulated value.
BOOL
FALSE
The block has an initialization routine that is processed when the
COM_RST input is set.
BOOL
TRUE
If the input "Enable manual mode" is set then the control loop is inter-
rupted. The manual value MAN is set as manipulated value.
Function Manual, 03/2017, A5E35300227-AC