Behavior of the LEDs in the operating state

Table 7- 19
Description of the LEDs during operation of the CU310-2 PN
LED
Color
RDY
-
(READY)
Green
Red
Red/green
Orange
Green/oran
ge
or
red/orange
COM
-
Green
Red
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
State
Description / cause
OFF
The electronics power supply is missing or
outside the permissible tolerance range.
Continuous light
The unit is ready for operation.
Cyclic DRIVE-CLiQ communication is in
progress.
Flashing light 0.5
Commissioning/reset
Hz
Flashing light 2 Hz Writing to the memory card.
Flashing light
General fault
2 Hz
Flashing light
The control unit is ready for operation, but there
0.5 Hz
are no software licenses.
Flashing light
Updating the firmware of the DRIVE-CLiQ
0.5 Hz
components.
Flashing light
DRIVE-CLiQ component firmware update
2 Hz
completed. Waiting for POWER ON of the
corresponding components.
Flashing light
Recognition of the component via LED is
2 Hz
activated (see SINAMICS S120/S150 List
Manual.)
Note:
Both options depend on the LED status when
component recognition is activated.
OFF
Cyclic communication has not (yet) taken place.
Note:
PROFIdrive is ready for communication when
the Control Unit is ready (see LED: RDY).
Continuous light
Cyclic communication is taking place.
Flashing light
Full cyclic communication is not yet taking place.
0.5 Hz
Possible causes:
The controller is not transferring any
setpoints.
During isochronous operation, no GC (Global
Control) or a faulty GC is transferred by the
controller.
Flashing light
The PROFIBUS master is sending a faulty
0.5 Hz
parameter assignment or the configuration file is
corrupted.
Flashing light
Cyclic bus communication has been interrupted
2 Hz
or could not be established.
Control Units, Control Unit Adapters and operating components
7.3 Control Unit CU310-2 PN (PROFINET)
Remedy
Check the power
supply
-
-
-
Check parameter
assignment/configurati
on
Install the missing
licenses.
-
Switch on the
component.
-
-
-
-
Modify the
configuration between
master/controller and
control unit.
Rectify the fault in bus
communication.