Switching Off The Storage System - Bosch BPT-S 5 Hybrid User Manual

Solar inverter
Hide thumbs Also See for BPT-S 5 Hybrid:
Table of Contents

Advertisement

Available languages

Available languages

38 | Operation
DANGER
NOTICE
Storage system | User manual
Info
In order to be able to use, store or feed the energy
that is generated by the photovoltaic system, you
must ensure that the DC disconnecting switch is
switched on.
4.2

Switching off the storage system

Risk of electric shock
The device's voltage supply comes from various
sources.
Follow the sequence for switching off the system
described in the instruction manual
Switch off the energy supply from the PV system
(external isolator)
Observe the 13-minute time period until the device
is fully de-energised
Data loss caused by switching the system off
incorrectly
If you do not follow the sequence for switching off
the system as described in the instruction manual,
system data and settings may be lost.
Always shut down the storage system first via the
EMS system menu
Only press the On/Off switch after the system has
shut down completely.
Procedure
1. EMS start window: Press System shutdown
The System shutdown window opens.
English
Bosch Power Tec GmbH

Advertisement

Table of Contents
loading

Table of Contents