Start Up; System Start Up - Bosch 19 SEER Series Operation Manual

Inverter ducted packaged heat pump
Table of Contents

Advertisement

Installation & Operation Manual
WARNING: ELECTRICAL SHOCK
Label all wiring prior to disconnection when
servicing controls. Wiring errors can cause improper
and dangerous operation. Verify proper operation
after servicing.
Compressors
(each)
Voltage
Size
- Phase -
(Tons)
Frequency
RLA
LRA
60
208/230-
27A
52A
(5.0)
1-60
Table 8
Electrical Data Without Electric Heat
Heater Circuit
Model
kW
Stages
EHK-05J
3.8/5
1
EHK-08J
5.6/7.5
1
EHK-10J
7.5/1.0
1
EHK-15J
11.3/15
2
EHK-20J
15/20
2
Table 9
Electrical Data With Electric Heat
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per Standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or fi eld installed.
* Max Fuse/Breaker Sizes listed in Table 9 are for electric heater ONLY. DOES NOT
include breaker size for the unit (refer to Table 8).
WARNING: ELECTRICAL SHOCK / FIRE HAZARD
Any power supply and circuits must be wired and
protected in accordance with local electrical codes.
BTC 761701105 A | 03.2019
OD Fan
Supply
Motors
Blower
Unit Circuit
(each)
Motor
Max Fuse²/
MCA¹
FLA
FLA
Breaker³ Size
(Amps)
(Amps)
2.1A
6.0A
41.9
60
Max Fuse²/
MCA¹
Amps
Breaker³
(Amps)
Size (Amps)*
18.1/20.8
23/26
25/30
27.1/31.3
34/40
35/40
36.1/41.7
46/53
50/60
54.2/62.5
68/79
70/80
72.2/83.3
91/105
100/110
Bosch Inverter Ducted Packaged Heat Pump | 19

11 Start Up

11.1 System Start Up

1.
Ensure Sections 4, 5, 6, 7, and 8 have been completed.
2.
Set System Thermostat to OFF.
Figure 18
3.
Turn on disconnect to apply power to the indoor and outdoor units.
Figure 19
4.
Wait one (1) hour before starting the unit if compressor crankcase
heater is used and the outdoor ambient temperature is below 70 °F.
60 MIN.
Figure 20
5.
Set system thermostat to ON.
Figure 21
ON
OFF
Data subject to change

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Brb-60hwd1n1-m19

Table of Contents