Cautions
• A watchdog timer error may occur when many numbers of points are transferred in one operation cycle. In such a
case, take one of the following countermeasures:
- Change the watchdog timer time
By overwriting the contents of D8000 (watchdog timer time), the watchdog timer detection time is changed (initial
value: K200).
When the program shown below is input, the sequence program will be monitored with the new watchdog timer
time.
M8002
0
Initial pulse
- Change the number of transferred points "n2" in each operation cycle
Change the number of transferred points "n2" in each operation cycle to a smaller value.
• Do not stop the driving of the instruction while it is being executed. If driving is stopped, the buffer memory (BFM)
reading/writing processing is suspended, but the data acquired in the middle of reading/writing processing is stored
in
D
and later and buffer memories (BFM).
Command
input
M
M8029
Instruction execution complete
• When indexing is executed, the contents of index registers at the begining of execution are used.
Even if the contents of index registers are changed after the instruction, such changes do not affect the process of
the instruction.
• The contents of "n1" devices starting from
execution of the instruction is completed, execute another instruction for "n1" devices starting from
• Do not update (change) the contents of "n1" devices starting from
executed. If the contents are updated, the intended data may not be written to the buffer memories (BFM).
• Do not update (change) the contents of "n1" buffer memories (BFM) starting from the buffer memory No. "m2" while
the RBFM (FNC278) instruction is executed. If the contents are updated, the intended data may not be read.
702
FNC 12
MOV
Watchdog timer refresh
FNC 07
When WDT (FNC 07) instruction is not programmed, the value
WDT
of D8000 becomes valid during END processing.
FNC278
m1
m2
RBFM
Watchdog timer time: 300 ms
K300
D8000
SET
M
D
n1
n2
RST
M
D
change while the RBFM (FNC278) instruction is executed. After
S
31 Data Transfer 3 – FNC276 to FNC279
31.1 FNC278 – RBFM / Divided BFM Read
while the WBFM (FNC279) instruction is
D
.