Mitsubishi Electric FX3G SERIES Programming Manual page 388

Programmable controllers
Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
3. Handling of pulse output terminals in FX
The outputs Y000 and Y001 are the high-speed response type.
When using a pulse output instruction or positioning instruction, adjust the load current of the open collector transistor
output to about 10 to 100 mA (5 to 24V DC).
Item
Operating voltage range
Operating current range
Output frequency
When the load is smaller, connect a dummy resistor in parallel to the outside of a used output terminal (Y000 or Y001)
as shown in the circuit diagram below so that the specified current shown above flows in the output transistor.
Equipment
load
resistor
External
power
supply
4. Cautions on special high-speed output adapters
1)
Outputs of special high-speed output adapters work as differential line drivers.
2)
Set the pulse output type setting switch in a special high-speed output adapter to the "pulse chain + direction"
(PLS DIR) side.
If the switch is set to the "forward rotation pulse chain reverse rotation pulse chain" (FP RP) side, normal
operations are disabled. The pulse output destination changes depending on the PLC output status as shown in
the table below.
Pulse output
destination
=
Y000
D
=
Y001
D
3)
Set the pulse output type setting switch while the PLC is stopped or while the power is OFF.
Do not manipulate the pulse output type setting switch while pulses are being output.
4)
When special high-speed output adapters are connected, the same output numbers in the main unit are assigned
as shown in the table below.
Only wire the appropriate output terminals.
Outputs in special high-speed output adapters and the main unit operate as shown below.
Assignment of output numbers in special high-speed output adapter
Setting status of output form
setting switch
"FP RP" side
"PLS DIR" side
Output operation
Relay output type/triac output type main
unit
Special high-speed output adapter
Transistor output type main unit
386
Description
5 to 24V DC
10 to 100 mA
100 kHz or less
Dummy
resistor
Input circuit
Output affecting
operation
While Y004 is ON, pulses are output from Y000 in the high-speed output adapter.
Y004
While Y004 is OFF, pulses are output from Y004 in the high-speed output adapter.
While Y005 is ON, pulses are output from Y001 in the high-speed output adapter.
Y005
While Y005 is OFF, pulses are output from Y005 in the high-speed output adapter.
Signal name
Forward rotation pulse
chain (FP)
Reverse rotation pulse
chain (RP)
Pulse chain
Direction
While instruction is active, associated output is ON. (LED is also ON.)
Use a special high-speed adapter.
Set the output frequency to "200kHz" or less.
Set the output frequency to "100kHz" or less.
13 High-Speed Processing – FNC 50 to FNC 59
13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup
, FX
and FX
3G
3U
3UC
PLC
(transistor output)
[sink output]
Y000
COM1
Setting name in each
positioning instruction
Pulse output destination
Rotation direction signal
Pulse output destination
Rotation direction signal
series main units
Operation
Output number
1st unit
1st axis
2nd axis
Y000
Y001
Y004
Y005
Y000
Y001
Y004
Y005
Output operation
2nd unit
3rd axis
4th axis
Y002
Y003
Y006
Y007
Y002
Y003
Y006
Y007

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3u seriesFx3uc series

Table of Contents