FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
4. Output drive side
The following two circuits offer the same operation:
<OUT instruction>
X010
X010
M 6
In each circuit, M6 is ON during only one operation cycle when X010 turns from OFF to ON.
<Rising edge detection>
X020
FNC 12
MOV
In each circuit, MOV instruction is executed only once when X020 turns from OFF to ON.
=
M6
Operation
Operation
cycle
cycle
=
K10
D0
7.5 LDP, LDF, ANDP, ANDF, ORP, ORF
<Pulse instruction>
X010
PLS
M6
<Pulse instruction (applied instruction)>
X020
FNC 12
K10
MOVP
7 Basic Instruction
D0
195
1