ABB i-bus
KNX
Commissioning
Flash if object "Switch" is
Options:
Here you set the value of the communication object Switch, at which the output flashes. Flashing is not
retriggerable.
•
1: Flashing starts when a telegram with the value 1 is received on the communication object Switch. A
telegram with the value 0 ends flashing.
•
0: Flashing starts when a telegram with the value 0 is received on the communication object Switch. A
telegram with the value 1 ends flashing.
•
1 or 0: A telegram with the value 1 or 0 triggers flashing. Suspension of flashing is not possible in this
case.
Time for ON in sec [0...65,535]
Options:
This time for ON defines how long the output is switched ON during a flashing period. The smallest value
is 1 second.
Note
Only a certain number of switching actions are possible per minute and Energy Actuator. With frequent
switching, a switching delay can occur, as only a certain number of switching actions are possible per
minute, see
Time for OFF in sec [0...65,535]
Options:
This time for OFF defines how long the output is switched ON during a flashing period. The smallest value
is 1 second.
Note
Only a certain number of switching actions are possible per minute and Energy Actuator. With frequent
switching, a switching delay can occur, as only a certain number of switching actions are possible per
minute, see
64 2CDC 505 084 D0203 | SE/S 3.16.1
1
0
1 or 0
0....5...65,535
Technical
data, page 7. The same applies directly after bus voltage recovery.
0....5...65,535
Technical
data, page 7. The same applies directly after bus voltage recovery.