Mitsubishi Electric PURY-P72 Service Handbook page 30

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[II
Restrictions]
2. M-NET Address settings
(1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
Unit or controller
Sym-
Address
Setting method
Factory
bol
setting
address
range
setting
CITYMULTI
Main/sub unit
IC
0, 01 to
Assign the smallest address to the main indoor unit in the
00
indoor unit
50*1 *4 *6
group, and assign sequential address numbers to the rest
M-NET
of the indoor units in the same group.
In an R2 system with a sub BC controller, make the set-
adapter
tings for the indoor units in the following order.
M-NET con-
(i) Indoor unit to be connected to the main BC controller
trol interface
(ii) Indoor unit to be connected to sub BC controller 1
(iii) Indoor unit to be connected to sub BC controller 2
Free Plan
Make the settings for the indoor units in the way that the
adapter
formula "(i)
<
(ii)
<
(iii)" is true.
LOSSNAY, OA processing unit
LC
0, 01 to
Assign an arbitrary but unique address to each of these
00
50*1 *4 *6
units after assigning an address to all indoor units.
M-NET re-
Main remote
RC
101 to
Add 100 to the smallest address of all the indoor units in
101
mote con-
controller
150
the same group.
troller
Sub remote
RC
151 to
Add 150 to the smallest address of all the indoor units in
controller
200*3
the same group.
MA remote controller
MA
No address settings required. (The main/sub setting must be made if
Main
2 remote controllers are connected to the system.)
CITY MULTI outdoor unit
OC
0,51 to
<Assign an address that equals the lowest address of the in-
00
OS
100*1 *2
door units in the same refrigerant circuit plus 50.
*6
<Assign sequential addresses to the outdoor units in the
same refrigerant circuit. The outdoor units in the same re-
friger!!"t circuit are automatically designated as OC and
as.
Auxiliary
BC controller
BC
0,51 to
<Assign an address that equals the address of the outdoor
00
outdoor unit
(main)
100*1 *2
unit in the same refrigerant system plus 1.
*6
-If a given address overlaps any of the addresses that are
assigned to the outdoor units or to the sub BC controller,
use a different, unused address within the setting range.
BC controller
BS1
51 to
-Assign an address to both the sub BC controller 1 and 2
(sub1,2)
BS2
100 *2
that equals the lowest address of the indoor units that
are connected to each of them plus 50.
-If a sub BC controller is connected, the automatic startup
function is not available.
System
Group remote con-
GR
201 to
Assign an address that equals the sum of the smallest
201
controller
troller
SC
250
group number of the group to be controlled and 200.
System remote con-
SR
Assign an arbitrary but unique address within the range
troller
SC
listed on the left to each unit.
ON/OFF remote con-
AN
Assign an address that equals the sum of the smallest
troller
SC
group number of the group to be controlled and 200.
Schedule limer (com-
ST
Assign an arbitrary bul unique address within the range
202
patible with M-NET)
SC
listed on the left to each uni!.
Central controller
TR
0,201 to
Assign an arbitrary but unique address within the range
000
G(B)-50A
SC
250
listed on the left to each unit. The address must be set to
"0" to control the K-control unit.
LM adapter
SC
201 to
Assign an arbitrary but unique address within the range
247
250
listed on the left to each unit.
*1. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the
setting range.
*2. To set the outdoor unit address or the auxiliary outdoor unit address to "100," set the rotary switches to "50."
*3. To set the M-NET remote controller address to "200," set the rotary switches to "00."
*4. Some models of indoor units have two or three
control
boards.
Assign an address to the No.1, No.2, and NO.3 control boards so that the NO.2 control board address equals the NO.1 control
board address plus 1, and that the No.3 control board address equals the NO.1 control board address plus 2.
*5. The outdoor units in the same refrigerant circuit are automatically designated as OC, and
as.
They are designated as OC,
and OS in the descending order of capacity (ascending order of address if the capacities are the same).
*6. No address settings are required for units in
a
system with a single outdoor unit (with some exceptions).
Address setting is required if a sub
Be
controller is connected.
HWEOB03A
- 20-
GB

Advertisement

Table of Contents
loading

Table of Contents