[Vln Test Run Mode]
(2) Heating only operation
Outdoor unit model
Operation
PURY-P72THMU-A
PURY-P96THMU-A
Model name of BC controller
CMB-P104NU-G
CMB-P104NU-G
Indoor
21.1°C/-
21.1°C/-
Ambient
[70°
F/-]
[7O°F/-]
tempera-
DBIWB
ture
Outdoor
B.3°C/6.1°C
8.3°C/6.1°C
[47°F/43°F]
[47°F/43°F]
No. of connected units
3
2
Unit
Indoor unit
No. of units in operation
3
2
Operating
Model
-
24/24/24
48/48
conditions
Main pipe
5
[16-3/8"]
5
[16-3/8"]
Piping
Branch pipe
m
10
[32-3/4"]
10
[32-314"]
[tt]
Total pipe length
35
[114-13/16"]
25 [82]
Fan speed
-
Hi
Hi
Amount of refrigerant
kg
19.1
[42J
21.3 [47J
[Ibs-oz]
Electric current
A
16.8
24.1
Outdoor
Voltage
V
230
230
unit
Compressor frequency
Hz
48
71
LEV open-
Indoor unit
205/203/200
406/406
Pulse
ing
BC controller
(112/3)
1101-/520
1101-/590
High pressure(63HS1)1
2.61/0.69
2.6710.68
Pressure
Low pressure(63LS)
MPa
[378/100]
[387/98J
BC controller on the liquid side(PS1)1
[psi]
2.54/2.22
2.63/2.31
Intermediate part(PS3)
[368/321]
[381/335]
Discharge (TH4)
69 [156J
80 [176]
Heat exchanger outlet
0 [32]
0 [32J
(TH6)
Outdoor
Accumulator inlet
1 [34]
-2 [28]
Temp. of
unit
each sec-
Accumulator outlet
°C
1 [34]
-3 [27]
tion
Compressor inlet
[OF]
1 [34]
[27]
-3
Compressor shell bottom
40 [104]
40 [104]
LEV inlet
30 [86]
38 [100]
Indoor unit
Heat exchanger inlet
63
[145]
70 [158]
HWE0803A