[VIII
Test Run Mode J
Outdoor unit model
Operation
PURY-P192TSHMU-A
PURY-P96THMU-A
I
PURY-P96THMU-A
Model name of BC controller
CMB-P108NU-GA
Ambient
Indoor
26.7"C/19.4°C [80° F/67° FJ
tempera-
DBIWB
ture
Outdoor
35°C/- [95°F/-J
No. of connected units
6
Unit
Jndoorunit
No. of units in operation
6
Model
-
30/30/30/30/36/36
Operating
conditions
Main pipe
5 [16-3/8'1
Piping
Branch pipe
m
10 [32-3/4"J
[ftJ
Total pipe length
65 [213-1/4'7
Fan speed
-
Hi
Amount of refrigerant
kg
42.4 [93J
[lbs-ozJ
Electric current
A
47.5
Outdoor
Voltage
V
230
unit
Compressor frequency
Hz
65
65
lEV open-
Indoor unit
230/230/230/230/275/275
Pulse
ing
BC controller (1/2/3)
2000/2000/270
High pressure(63HS1)/
2.66/0.93
2.66/0.93
Low pressure(63LS)
MPa
[385/134J
[385/134J
Pressure
BC controller on the liquid side(PS1)1
[psiJ
2.59/2.59
Intermediate part(PS3)
[375/375J
Discharge (TH4)
85 [185]
85 [185J
Heat exchanger outlet
39 [102J
39 [102J
(TH3)
Outdoor
Accumulator inlet
8 [46J
8 [46J
Temp. of
unit
each sec-
Accumulator outlet
°C
8 [46]
8 [46]
tion
Compressor inlet
[OF]
19 [66]
19 [66J
Compressor shell bottom
42 [108]
40 [104]
LEV inlet
19 [66]
Indoor unit
Heat exchanger inlet
6 [43J
HWEOB03A
- 169-
GB