Mitsubishi Electric PURY-P72 Service Handbook page 174

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[VIII Test Run Mode]
Outdoor unit model
Operation
PURY-P120THMU-A
Model name of BC controller
CMB-P104NU-G
Indoor
26.7°C/19.4°C
Ambient
[80°F/67°F]
tempera-
DBIWB
ture
Outdoor
35°C/-
[95°F/-]
No. of connected units
4
Unit
Indoor unit
No. of units in operation
4
Operating
Model
-
30/30/30/30
conditions
Main pipe
5 [16-3/8j
Piping
Branch pipe
m
10 [32-3/4j
[It]
Total pipe length
45 [147-5/8j
Fan speed
-
Hi
Amount of refrigerant
kg
22.5 [50]
[Ibs-oz]
Electric current
A
29.5
Outdoor
Voltage
V
230
unit
Compressor frequency
Hz
75
LEV open-
Indoor unit
230/230/230/230
Pulse
ing
BC controller (1/2/3)
2000/-/210
High pressure(63HS1)/
2.82/0.89
Pressure
Low pressure(63LS)
MPa
[409/129]
BC controller on the liquid side(PS1)/
[psi]
2.73/2.72
Intermediate part(PS3)
[395/394]
Discharge (TH4)
82 [180]
Heat exchanger outlet
43 [109]
(TH3)
Outdoor
Accumulator inlet
8 [46]
Temp. of
unit
each sec-
Accumulator outlet
°C
8 [46]
tion
Compressor inlet
[oF]
20 [68]
Compressor shell bottom
42 [108]
LEV inlet
22 [72J
Indoor unit
Heat exchanger inlet
11
[52]
HWE0803A
- 164-
GB