Mounting, Installation And Commissioning; Maintenance; Change Of Batteries; Technical Data - Siemens RDH10RF User Manual

Wireless room temperature controller with large lcd non-programmable, for heating or cooling systems
Hide thumbs Also See for RDH10RF:
Table of Contents

Advertisement

Mounting, installation
and commissioning

Maintenance

Change of batteries

Reset

Technical data

Power supply
Sensor inputs
Operational data
Environmental conditions
Siemens
Building Technologies
When mounting the controller, fix the baseplate first. The receiver does not require a
baseplate. Make the electrical connections and fit and secure the receiver (also refer to
the separate mounting instructions).
Mount the controller on a flat wall and in compliance with local regulations.
If there are thermostatic radiator valves in the reference room, set them to their fully
open position.
Controller and receiver are maintenance-free.
If battery symbol
appears, the batteries are almost exhausted and must be re-
placed.
To reset the controller, press both the Test and Learn buttons on the rear of the unit.
To reset the receiver, press the RESET button on the unit front.
All individual settings are then reset to their default values.
Operating voltage
Battery life
Internal:
Thermistor
Switching differential SD
Setpoint setting range
Factory setting comfort setpoint
Resolution of settings and displays
Setpoints
Actual value displays
Operation
Climatic conditions
Temperature
Humidity
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Storage
Climatic conditions
Temperature
Humidity
Room temperature controllers
DC 3 V (2 x 1.5 V AA alkaline batteries)
>1 year (AA alkaline batteries)
10 kΩ ± 1% at 25 °C
1 K
5...30 °C
20 °C
0.5 °C
0.5 °C
IEC 721-3-3
Class 3K5
0...+40 °C
<90% r.h.
IEC 721-3-2
Class 2K3
-25...+60 °C
<95% r.h.
Class 2M2
IEC 721-3-1
Class 1K3
-10...+60 °C
<90% r. h.
5/10
CE1N3070en
20.11.2007

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RDH10RF and is the answer not in the manual?

Questions and answers

Peter Draper
February 9, 2025

i have changed battery but stat is not working properly

1 comments:
Mr. Anderson
February 11, 2025

The Siemens RDH10RF thermostat may not be working properly after changing the battery due to one or more of the following reasons:

1. Factory Reset: If the RESET button was accidentally pressed during battery replacement, the thermostat may have returned to factory settings, requiring reconfiguration.
2. Low Battery Power: If the new batteries are not fully charged or are not AA alkaline batteries as required, the thermostat may not function correctly.
3. Incorrect Battery Installation: The batteries might be inserted incorrectly, preventing proper operation.
4. Loss of Connection: If the thermostat is wireless (RF model), it may have lost communication with the receiver and needs to be re-paired.
5. Internal Memory Loss: Removing the batteries may have erased stored settings, requiring the thermostat to be set up again.

To resolve the issue, ensure the correct battery type and polarity, check for a communication reset if applicable, and reconfigure the thermostat settings if needed.

This answer is automatically generated

This manual is also suitable for:

Rdh10 setRdh100

Table of Contents

Save PDF