The RDH 100 is used to control the room temperature in heating systems.
Typical applications:
The device is used together with the following equipment:
RDH100 offers both 2-position and PID intelligent learning temperature control, configurable via parameter P01 (control behaviour).
2-position control algorithm is to switch on and off the heating system within a switching differential (SD) as per difference between setpoint setting and measured room temperature.
PID intelligent learning control algorithm periodically switches on and off the heating system. The period time (T) and pulse length (P) of the control signal (PWM) are determined by the setpoint and the measured room temperature.
In general, PID control provides more comfort and is more energy efficient than 2-position control.
The factory setting for control is "PID slow", ideal for most heating systems. Optimum control can be selected if control does not provide the desired result:
2-position, 1 K
2-position controller with 1 [K] switching hysteresis
Typical applications:
2-position, 0.5 K
PID slow
PID control behaviour for slow heating systems that require longer minimum On times and a limited number of switching cycles per hour.
Typical applications:
Minimum switch on/off time | > 4 minutes |
Minimum period | Approximately 12 minutes |
PID fast
PID control behaviour for fast heating systems that tolerate a high number of switching cycles.
Typical applications:
Minimum switch on/off time | > 1 minute |
Minimum period | Approximately 6 minutes |
Do not use PID fast for oil boilers or electric mechanical actuators!
When removing the batteries, the setpoints and information required for operating mode changeover are retained for max. 2 minutes.
Parameter list
Parameter | Description | Factory setting | Setting range | Remark |
P01 | Control behavior | PID slow (4) | 0 = 2P, 1.0 K 1 = 2P, 0.5 K 2 = PID fast 4 = PID slow | |
P02 | Maximum temperature range | 30°C | P03...30°C | Limit of comfort and economy setpoint |
P03 | Minimum temperature range | 5°C | 5°C...P02 | Limit of comfort and economy setpoint |
End | Exit parameter setting |
Parameter setting
The parameter setting remains in non-volatile memory and is not erased when the battery is removed. The reset function on the rear of the thermostat reloads the factory settings.
![]() | Parameter setting mode
|
Note: The thermostat automatically exits parameter setting mode one minute after the last action.
Description | Product number | Data sheet *) | |
Electrothermal actuator (for radiator valves) | ![]() | STA23.. | 4884 |
Electrothermal actuator (for small valves 2.5mm) | ![]() | STP23.. | 4884 |
Electromotoric actuator | ![]() | SFA21.. | 4863 |
*) The documents can be http://siemens.com/bt/download.
The digital display shows the current room temperature and the comfort temperature setpoint. When the heating output is active, the triangle symbol is displayed.
When ordering, specify both name and product number, e.g. room temperature controller RDH100.
Order valves and actuators as separate items.
The device consists of 3 parts:
The housing engages in the baseplate and snaps on. The baseplate carries the screw terminals.
There is a reset button on the rear of the device.
Elements | 1 | ![]() | Display of the room temperature in °C / °F |
2 | ![]() | Indicates a request for heating | |
3 | Temperature setting knob | ||
4 | Battery compartment | ||
5 | ![]() | Comfort temperature setpoint | |
6 | ![]() | Indicates low battery power; replace batteries |
Topic | Title | Document ID: |
Operating | Operating instructions | A6V101035984 |
Installation | Mounting instructions | A6V10974417 |
CE declaration | A6V101123363 |
Related documents such as CE declaration, etc., can be downloaded at the following address: http://siemens.com/bt/download.
When mounting the device, attach the baseplate first. Then, make the electrical connections, and fit and secure the device (refer to the separated mounting instructions A6V10974417). Mount the device on a flat wall and in compliance with local regulations.
If the reference room contains thermostatic radiator valves, set them to their fully open position.
No internal line protection for supply lines to external consumers.
Risk of fire and injury due to short-circuits!
If the battery symbol appears, the batteries are almost empty and must be replaced.
To reset, press the reset button on the rear of the device. This resets all individual settings to their default values.
The device is maintenance-free.
The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage.
Instructions for the replacement of alkaline batteries
Explosion due to fire or short-circuit, even with discharged batteries
Risk of injury due to flying parts
Leakage of electrolyte
Severe burns
Observe the following:
Power supply | ||
Operating voltage | DC 3 V (2 x 1.5 V AA alkaline batteries) | |
Battery life | >1 year (with AA alkaline batteries) | |
Internal sensor inputs | ||
Thermistor | 10 ![]() | |
Switching outputs (Lx, L1, L2) | ||
Relay contacts | Switching voltage | Max. AC 250 V Min. AC 24 V |
Switching current | Max. 5 A res., 2 A ind. | |
At AC 250 V | Min. 8 mA | |
Insulating strength | Between relay contacts and coil | AC 3,750 V |
Between relay contacts (same pole) | AC 1,000 V |
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line required under all circumstances.
Operational data | |||
PID control: | Slow | Fast | |
Minimum period | 4 min | 2 min | |
Minimum pulse length | 12 min | 6 min | |
RDH100 | |||
Setpoint setting range | 5...30°C | ||
Factory setting comfort setpoint | 20°C | ||
RDH100/SPL | |||
Setpoint setting range | 15...30°C | ||
Factory setting comfort setpoint | 20°C | ||
Resolution of settings and displays | Temperature setpoint | 0.5°C | |
Display of actual temperature value | 0.5°C | ||
Electrical connections | |||
Connections terminals (via baseplate) | Screw terminals | ||
For solid wires | 2 x 1.5 mm2 | ||
For stranded wires | 1 x 2.5 mm2 (min. 0.5 mm2) |
Environmental conditions
Operation | IEC 60721-3-3 |
Climatic conditions | Class 3K5 |
Temperature | 0...+40°C |
Humidity | <90% r.h. |
Transport | IEC 60721-3-2 |
Climatic conditions | Class 2K3 |
Temperature | -25...+60°C |
Humidity | <95% r.h. |
Mechanical conditions | Class 2M2 |
Storage | IEC 60721-3-1 |
Climatic conditions | Class 1K3 |
Temperature | -10...+60°C |
Humidity | <90% r.h. |
Standards, directives and approvals
EU conformity (CE) | A6V101123363 *) |
RCM conformity | A6V11161600 *) |
Safety class | II as per EN 60730-1 |
Pollution degree | 2 |
Degree of protection of housing | IP20 |
Eco design and labeling directives | Based on EU Regulation 813/2013 (Eco design directive) and 811/2013 (Labeling directive) concerning space heaters, the following classes apply: Application with On/Off operation of a heater Class I Value 1% PWM (TPI) room thermostat, for use with On/Off output heaters Class IV Value 2% |
Environmental compatibility | The product environmental declaration (A6V101123358 *)) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). |
*) The documents can be http://siemens.com/bt/download.
General
Weight (including package) | 350 g |
Color of housing front | Signal-white RAL9003 |
Housing material | ABS (LCD lens: PC) |