Toshiba BMS-SM1280HTLE Service Manual page 7

Smart manager
Hide thumbs Also See for BMS-SM1280HTLE:
Table of Contents

Advertisement

System Devices Configuration
Device Name
Indoor Unit
Energy Monitoring Relay Interface
Digital Input / Output Relay Interface BMS-IFDD03E
Central Remote Controller
Client PC
Client PC spec
2-1. Communication Specification
TCC-LINK
Topology
Signal wire type
Wire size, length
Number of nodes
Transmission rate
Polarity
RS-485
Topology
Signal wire type
Transmission distance
Number of nodes
Transmission rate
Polarity
Ethernet
Network interface
Transmission rate
Transmission media
Straight / Crossover
Length
Connection
Model
(TCC-LINK based model)
BMS-IFWH5E
TCB-SC642TLE
BMS-CM1280TLE
(Windows based model)
OS
Browser
Display
Bus
2-core shield wire
2
For 1.25mm
(AWG16), up to 1,000 m (Total length)
2
For 2.00mm
(AWG14), up to 2,000 m
Up to 100
(Total of Indoor unit, Outdoor unit, Central Remote Controllers and Interfaces)
9.6kbps
Not exist
Bus
2-core shield wire
Up to 500 m (Total length)
Up to 32
115.2kbps
Exist
10BASE-T / 100BASE-TX (Auto sensing)
10 M bps (10BASE-T)
100 M bps (10BASE-TX)
For 10BASE-T: Category 3 or Category 5
For 100BASE-TX: Category 5 (*)
Use a straight or crossover cable depending on use.
Maximum segment length: 100 m
RJ-45 connector
7
EXTENDED SYSTEM
Number of Units
Connected
Up to 64 units per line
Max 128
Up to 128 units in total for 2 lines
Up to 8 electric energy meters per
Max 4
BMS-IFWH5E
Up to 8 lock inputs or fire alarm
Max 4
inputs per BMS-IFDD03E
Max10
Up to 4 units for simultaneous
access
Windows XP, Vista, 7
Internet Explorer 6.0 / 7.0 / 8.0 or Firefox 2.0 / 3.0 / 3.5 / 3.6
1,024 X 768 more
(*) LAN cable: Unshielded twisted pair (UTP)
Remarks

Advertisement

Table of Contents
loading