Toshiba BMS-SM1280HTLE Service Manual page 41

Smart manager
Hide thumbs Also See for BMS-SM1280HTLE:
Table of Contents

Advertisement

No.
Questions
15
Is connection available via the Internet (WAN)?
16
Is connection available from a mobile phone?
17
If a failure occurs on the air conditioner, can mail be
sent?
18
Can a tenant name or other names be changed?
19
Up to how many characters can be used for the name
of tenant, etc.?
20
How many items does the alarm history save?
21
How many days of power distribution data does the
system save?
22
Can data be maintained in case of power outage?
23
Does turning off the controller require any specific
operation?
24
Does turning off the controller stop the air conditioner? The air conditioner where the remote controller or wireless adaptor is
25
Does a scheduled operation work only if a PC remains
connected?
26
Does a PC need to remain connected to save power
distribution data?
27
Is it possible to know an air conditioner failure without
connecting a PC?
28
How many master schedules can be created?
29
How many billing schedules can be created?
30
What are the PC requirements for connecting to the
controller?
31
Can a schedule be separately set for each air
conditioner?
32
What is the billing schedule?
33
Can all the indoor units be made stop at a time?
34
Is monitoring the operation state of the outdoor unit
possible?
35
Does setting operation for an air conditioner have any
priority?
36
Is it possible to connect an indoor unit without its remote
controller?
37
Is connection available via VPN?
Not available.
Not possible.
You can use the Setting File Creation Software to change the name of a floor,
a tenant, an area, and an air conditioner.
For a floor name: 20 bytes,
for a tenant name: 30 bytes,
for an area name: 20 bytes, and
for an air conditioner name: 20 bytes.
It saves up to 1,024 items. If the alarm history items exceed 1,024, the item
is deleted sequentially from the oldest one.
The system saves the 45 days of daily report files and the 3 months of
monthly report files.
Data will be backed up before being saved. If power outage occurs during the
data saving, the backup data is restored, thus the data is protected.
No specific operation is necessary.
connected does not stop when the controller is turned off.
An air conditioner other than the above stops.
No. Because the power distribution data are saved inside the controller, the
PC does not need to remain connected.
An alarm can be set to go off with a buzzer or other means connected to the
alarm external output of no-voltage A contact.
An alarm can be set to go off with a buzzer or other means connected to the
alarm external output of no-voltage A contact.
Up to 32 schedules can be created for each master schedule and billing
schedule.
1.PC running Window XP or Vista without any problem. Also, the PC
must have Internet Explorer Version 6.0, 7.0 or 8.0 or Firefox 2.0, 3.0,
3.5 or 3.6.
2.If you use the Monthly Report Creation Software, you need to install
Microsoft Excel 2002 or later on your computer.
One air conditioner can register only one master schedule while 32 master
schedules can be created.
An operating schedule can be separately set for each air conditioner.
A day is divided into two time frames: on-hours and off-hours, and power is
distributed to each time frame.
For example, the billing schedule can be used to charge only for the
operation during overtime work hours.
Possible.
In the zone window of a PC, select all floors or all tenants and perform setting
for the stop.
For all the indoor units, set lock interlocking that is activated by the same lock
input. (The same as fire alarm interlocking setting)
Apply the external input of all stop to the controller.
Not possible.
The button pressed later receives priority.
Possible.
Available.