Connectors - GE 90*-30 PLC Series User Manual

Interface between a series 90-30 programmable logic controller (plc) and a lonworks network bus interface module
Hide thumbs Also See for 90*-30 PLC Series:
Table of Contents

Advertisement

Connectors

GFK-1322A
During normal operation, the only external connection to the LBIM is the network connection to
the two-pin removable header on the front panel. The RJ-45 connector is reserved for easy
connection of network management tools during configuration of the interface and binding of
network variables. The RS-422 serial port is used to update LBIM firmware and is not normally
needed by the user.
Table 1-4. LBIM Connectors
Connector
NETWORK
NETWORK
COM PORT RS-422
Series 90-30 backplane
Table 1-5. Pin Assignments for RS-422 Port
Pin
Signal Name
1
Shield
2
No connection
3
No connection
4
No connection
5
No connection
6
RTS (A)
7
OV
Chapter 1 Overview
Function
Connection of network
management tools
Provides L
W
network
ON
ORKS
field connection (NETA, NETB)
2
using 18-24 AWG (0.86mm
2
0.22mm
) twisted pair wires.
RS-422 serial port that supports
SNP communications (SNP and
SNPX). Used to update LBIM
firmware. (Does not support
Hand-Held Programmer.)
Connection to PLC backplane
Pin
Signal Name
8
CTS (B)
9
RT
10
RD (A)
11
RD (B)
12
SD (A)
13
SD (B)
14
RTS (B)
15
CTS (A)
Type
RJ-45
NetA, NetB
2-pin removable screw terminal
to
DB-15, female
24-pin connector
1
1-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents