D.20 Networks; Ordering Guide - GE D.20 RIO Hardware User Manual

Distributed i/o controller
Table of Contents

Advertisement

ORDERING GUIDE

D.20 networks

Ordering guide
16
In a redundant configuration, a D400 can be connected to eight D.20 RIOs, with each
redundant pair of D.20 RIOs providing communication with up to 30 peripherals.
Features of the D.20 RIO include:
Dual D.20 link channels support looped peripheral systems
Integration with the D400 Substation Gateway
Manages peripheral code and configuration downloads
LEDs for device power and status, D.20 TX and RX, and Ethernet link activity and
connect speed
10/100BaseT interface for D.20 protocol communication with the D400 Substation
Gateway
Optional low and high voltage power supply modules
Inserts power on the D.20 interface cable
1U 19 inch rack, DIN rail, or panel mounting options
All connectors are mechanically secured
Supports 802.3p and 802.3Q (VLAN) to ensure D.20 data receives higher priority
1 ms accuracy using SNTP time sync
1 ms accuracy recorded for 99.6% of the total D.20 RIO points. See "Product
specifications" on page 17 for more details.
A D.20 network enables GE Digital Energy devices to connect to D20-series peripherals. It
uses an HDLC protocol to acquire data from and to send commands to the peripheral
devices. The D.20 network supports the following peripheral modules:
D20 A - Analog input peripheral
D20 S - Digital (status) input peripheral
D20 K - Digital (control) output peripheral
D20 C - Combo peripheral available in three configurations (C0/C1/C2) providing
combinations of digital inputs (C0/C1/C2), digital outputs (C0/C1/C2), analog inputs
(C1/C2) and analog outputs (C2)
Table 2: D.20 RIO part numbers
Part
D.20 Distributed Network
Appliance
24 VDC Power supply
48 VDC Power supply
Description
This base unit includes rack mount flanges,
panel mount flanges, and DIN rail mount panel.
Input: 85 to 264 VAC, 45 to 65 Hz., or 90 to
350 VDC
Output: 24 VDC/ 3.5 A
DIN rail mount panel
Input: 85 to 264 VAC, 45 to 65 Hz., or 90 to
350 VDC
Output: 48 VDC/ 5A
DIN rail mount panel
GE Information
CHAPTER 1: BEFORE YOU START
GE Part Number
520-0231
580-3483
580-3484
D.20 RIO - HARDWARE USER'S MANUAL