Pr.
Pr.
422, 423, 425

Gain adjustment of position control

Pr.422 Position loop gain
Pr.425 Position feed forward command filter
Make adjustment of Pr.422 when any of such phenomena as
unusual vibration, noise and overcurrent of the motor/machine
occurs.
Increasing the setting improves trackability for the position
command and also improves servo rigidity at a stop, but oppositely
makes an overshoot and vibration more liable to occur.
Function of Pr.423 is designed to cancel a delay caused by the droop
pulses of the deviation counter. Primary delay filter relative to the
feed forward command can be input in Pr.425.
Pr.
Pr.
426, 427

Positioning adjustment parameter

Pr.426 In-position width
When the number of droop pulses has fallen below the value set in
Pr.426, the in-position signal (Y36) turns on.
When droop pulses exceed the value set in Pr.427, position error
large occurs and displays an error (E.OD) to stop the inverter.
Pr.
Pr.
450
Refer to the section about Pr.71.
Pr.
Pr.
451
Refer to the section about Pr.80.
Pr.
Pr.
453, 454
Refer to the section about Pr.80.
Pr.
Pr.
455 to 463
Refer to the section about Pr.82.
Pr.
Pr.
495 to 497

Remote output function (REM signal)

Pr.495 Remote output selection
Pr.497 Remote output data 2
You can utilize the on/off of the inverter's output signals instead of
the remote output terminal of the programmable logic controller.
Pr.
Pr.
503, 504

Maintenance of parts

Pr.503 Maintenance timer
When the cumulative energization time of the inverter reaches the
parameter set time, the maintenance timer output signal (Y95) is
output.
(MT) is displayed on the operation panel (FR-
DU07).
This can be used as a guideline for the maintenance time of
peripheral devices.
First power
ON
9998
(999800h)
Set "0" in Pr.503
Maintenance
Pr.504
timer
(Pr. 503)
OFF
ON
Y95 signal
MT display
The cumulative energization time of the inverter is stored into the
EEPROM every hour and indicated in Pr.503 Maintenance timer in
100h increments. Pr.503 is clamped at 9998 (999800h).
Pr.
Pr.
516 to 519
Refer to the section about Pr.29.
When setting parameters, refer to the instruction manual (applied) and understand instructions.
Vector
Vector
Vector
Pr.423 Position feed forward gain
Vector
Vector
Vector
Pr.427 Excessive level error
Pr.496 Remote output data 1
Pr.504 Maintenance timer alarm output set time
Time
ON
Pr.
Pr.
547, 548, 551
Inverter setup using USB communication
Pr.547 USB communication station number
Pr.551 PU mode operation command source selection
Inverter setup with setup software (FR-Configurator) can be easily
performed by USB communication.
When performing parameter setting with setup software, set "3" in
Pr.551PU mode operation command source selection.
Pr.
Setting
Number
Range
0
(initial
Set the station number of USB device (inverter)
547
value)
within the range "0 to 31".
1 to 31
Set the communication check time interval of USB
communication.
0 to 999.8
If data is not received within the time set in Pr.548,
548
9999
(initial
Communication time interval is not checked.
value)
Pr.
Pr.
549
Refer to the section about Pr.117.
Pr.
Pr.
550, 551
Refer to the section about Pr.338.
Pr.
Pr.
555 to 557
Current average value monitor signal
Pr.555 Current average time
Pr.557 Current average value monitor signal output reference current
The average value of the output current during constant speed
operation and the maintenance timer value are output as a pulse to the
current average value monitor signal (Y93).
The pulse width output to the I/O module of the PLC or the like can be
used as a guideline due to abrasion of machines and elongation of belt
and for aged deterioration of devices to know the maintenance time.
The current average value monitor signal (Y93) is output as pulse for
20s as 1 cycle and repeatedly output during constant speed operation.
From acceleration to constant speed operation
Y93 signal
1) Data output mask time
When the speed has changed to constant
from acceleration/deceleration, Y93 signal is
not output for Pr.556 time.
2) Start pulse
Output as Hi pulse shape for 1s (fixed)
Time and output current set in Pr.555 are averaged
3) Output current average value pulse
The averaged current value is output as low pulse shape for
0.5 to 9s (10 to 180%) during start bit output.
output current average value (A)
Signal output time=
Pr.557 (A)
Pr.
Pr.
563, 564
Refer to the section about Pr.52.
Pr.
Pr.
569
Refer to the section about Pr.80.
Pr.
Pr.
571
Refer to the section about Pr.13.
Pr.
Pr.
575 to 577
Refer to the section about Pr.127.
Pr.
Pr.
611
Refer to the section about Pr.57.
Pr.
Pr.
665
Refer to the section about Pr.882.
Pr.
Pr.
684
Refer to the section about Pr.82.
Pr.
Pr.
800
Refer to the section about Pr.80.
Pr.
Pr.
802
Refer to the section about Pr.10.
Pr.
Pr.
803
Refer to the section about Pr.22.
Pr.548 USB communication check time interval
Description
(E.USB) is displayed.
Pr.556 Data output mask time
Output
frequency
Time
1 cycle (20s)
Next cycle
5) End pulse
output as low pulse
shape for 1 to 16.5s
4) Maintenance timer pulse
The maintenance timer value (Pr.503) is output
as Hi output pulse shape for 2 to 9s (16000h to
72000h).
Pr.503
100h
5s
Signal output time=
40000h
5s
68